E3M220 MS5 Adapter
111
Building Technologies
001260_k_en_--.doc
Fire Safety & Security Products
02.2005
27
E3M220 MS5 Adapter
27.1 Overview
NOTE
The module E3M220 is
not
CE-conform!
z
Connection of
existing MS5 detectors
(220 VDC) to the CS1140 control unit
z
Converts the signal on the MS5 detection line into a conventional detector signal
(collective 20 V)
z
Designed for
2 detection lines with bi-directional signal conversion
z
Only use in combination with the E3M080 line module
z
Requires a separate supply 24 V
z
Card format (100 mm x 200 mm)
z
Number of MS5 detectors per detection line: FES5, DES5, MES5: unlimited
FES7.5:
max.
25
RES5, SES5:
max. 5
27.2 Key
data
Operating status of the MS5 detection line
Conversion
Operating status of the collective line
Alarm
AI
flashes
–>
Alarm
on corresponding line
Short circuit
< 40 V
Short circuit
on corresponding line
Open line
> 232 V
–>
Open line
on corresponding line
Converter failure
220 V missing
–>
Open line
on both detection lines
switched on
218 ... 232 V
<–
switched on
20 V on corresponding line
Reset
0 V
<–
Reset
0 V on corresponding line
OFF
0 V
<–
OFF
0 V on corresponding line
switched on
with autom. reset
<–
Detector test mode with autom. reset
Terminal block X10 (20 terminals)
–
mounted on module chassis
–
for the connection of the prefabricated cable to connection level, or
–
for direct connection of the periphery
Card chassis
–
mounted on module chassis
27.3 Interconnection
principle
E3M220
E3M080
Detection
line 1
Detection
line 2
220VDC
24VDC
24VDC
(20V)
(220V)
MS5 detectors
Detection line 1
Detection line 2