In this case, normalization with current I
c
will no longer work properly either. The normalization is canceled in
a phase-segregated manner. This means that the non-normalized value is used in place of the normalized
value (see
).
Charging/Energizing the Capacitor Bank or a Phase of the Bank
Charging of the bank takes place when the discharged bank is switched on to the network. Charging of a
phase can occur in case of network faults. If a phase-to-ground voltage drops to 0 V due to a network fault,
the respective phase is discharged and the return of the phase-to-ground (after the fault has been cleared) will
charge the phase.
Charging the bank or a phase of the bank causes inrush currents in the respective phases. To avoid overfunc-
tion in case of sensitive threshold settings, the stages using compensated unbalanced values are blocked in a
phase-selective way by setting I
unbal.,comp.
to 0 A. These stages are:
•
Counter stage
•
I> stage, if set to operate with compensated unbalanced values
The blocking (I
unbal.,comp.
set to 0 A) lasts for 250 ms after energizing detection. Afterwards, the calculated
I
unbal.,comp.
is processed again.
Energizing detection takes place in a phase-selective way by monitoring the phase current I
c
flowing into the
bank. If a phase current exceeds the threshold
Current Thresh.CB Open
, energizing in this phase is
detected.
Logic for Counting Faulty C-Elements
This part of the General functionality is only important if counter stages are used.
Capacitor Bank Protection
7.4 Current-Unbalance Protection for Capacitors, 3-Phase
SIPROTEC 5, Overcurrent Protection, Manual
981
C53000-G5040-C017-8, Edition 07.2017
Содержание 7SJ82
Страница 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...