Application and Setting Notes
Parameter: Maximum Differential Values of Voltage, Frequency and Angle
•
Default setting
(_:5071:122) Max. voltage diff. V2>V1
=
5.0 V
•
Default setting
(_:5071:123) Max. voltage diff. V2<V1
=
5.0 V
•
Default setting
(_:5071:117) Max. frequency diff. f2>f1
=
0.10 Hz
•
Default setting
(_:5071:118) Max. frequency diff. f2<f1
=
0.10 Hz
•
Default setting
(_:5071:124) Max. angle diff. α2>α1
=
10
o
•
Default setting
(_:5071:125) Max. angle diff. α2<α1
=
10
o
2 parameters are available for the differential values voltage, frequency, and angle. Unbalanced closing ranges
can be set with this, if required.
The permissible differential values must ensure that no protection tripping or damage occurs in the system
owing to compensation processes (circulating current) and power swings after interconnection of the parts of
the power system. The settings must not be configured too closely on the other side so that necessary
closures are not blocked.
Typical differential values are selected in the default setting. Depending on the system, the settings must be
checked and adjusted, if necessary.
Settings
Addr.
Parameter
C
Setting Options
Default Setting
General
_:5071:1
Synchrocheck 1:Mode
•
off
•
on
•
test
off
_:5071:101
Synchrocheck 1:Min.
operating limit Vmin
0.300 V to 340.000 V
90.000 V
_:5071:102
Synchrocheck 1:Max.
operat. limit Vmax
0.300 V to 340.000 V
110.000 V
_:5071:110
Synchrocheck
1:Max.durat.
sync.process
0.00 s to 3600.00 s; ∞
30.00 s
_:5071:108
Synchrocheck 1:Direct
close command
•
no
•
yes
no
_:5071:126
Synchrocheck 1:Voltage
adjustment
0.500 to 2.000
1.000
De-en.gized switch.
_:5071:105
Synchrocheck 1:Close
cmd. at V1< & V2>
•
no
•
yes
no
_:5071:106
Synchrocheck 1:Close
cmd. at V1> & V2<
•
no
•
yes
no
_:5071:107
Synchrocheck 1:Close
cmd. at V1< & V2<
•
no
•
yes
no
_:5071:103
Synchrocheck 1:V1, V2
without voltage
0.300 V to 170.000 V
5.000 V
_:5071:104
Synchrocheck 1:V1, V2
with voltage
0.300 V to 340.000 V
80.000 V
_:5071:109
Synchrocheck 1:Supervi-
sion time
0.00 s to 60.00 s
0.10 s
8.4.7.2
8.4.7.3
Control Functions
8.4 Synchronization Function
SIPROTEC 5, Overcurrent Protection, Manual
1143
C53000-G5040-C017-8, Edition 07.2017
Содержание 7SJ82
Страница 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...