As soon as an evolving fault is recognized (see chapter
6.45.4.13 Evolving-Fault Detection During Dead Time
),
a separate dead time for faults begins with the stopping of the fault. The total dead time is composed of the
part of the dead time that expired until the evolving fault was stopped for the 1st disruption plus the dead
time for the evolving fault. With the setting of the
Dead time aft. evolv. fault
to
invalid
, no
other automatic reclosing cycle is executed after tripping through the evolving fault. The tripping through
evolving faults is then finished.
[lopauare-010611-01.tif, 1, en_US]
Figure 6-308
Cyclic Automatic Reclosing Function - Logic of the Dead Time for the Operating Modes: With
Pickup
Evolving-Fault Detection During Dead Time
Evolving faults are short circuits, which occur after switching off a short circuit during dead time. This may be
the case during 1-pole tripping and there is a short circuit in the non-switched conductors after this.
After 3-pole tripping there may also be evolving faults if the line is fed through a second (non-3-pole) opened
circuit breaker, for example, for systems with a 1 1/2 circuit breaker layout.
6.45.4.13
Protection and Automation Functions
6.45 Automatic Reclosing Function
SIPROTEC 5, Overcurrent Protection, Manual
903
C53000-G5040-C017-8, Edition 07.2017
Содержание 7SJ82
Страница 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...