The functional measured values of Δφ in HMI are displayed differently in the following situations:
•
If the Vector-jump protection function is inactive, the function value of Δφ is displayed as “---”
•
If the Vector-jump protection function is active and has not picked up, the functional measured value of
Δφ is displayed as 0.0°
•
If the Vector-jump protection function is active and has picked up, the functional measured value of Δφ
is displayed as a calculated value (for example, 12.0°) and remains unchanged until the next pickup of
the Vector-jump protection function.
Application and Setting Notes
Parameter:
Threshold V1 min
•
Default setting
(_:2311:102) Threshold V1 min
=
46.189 V
With the parameter
Threshold V1 min
, you can define the minimum threshold of the voltage band.
The setting value is closed to the allowed lower limit of the voltage band. The default setting is 80 % of the
rated positive-sequence voltage. The value of the rated positive-sequence voltage is 100 V/√3.
Parameter:
Threshold V1 max
•
Default setting
(_:2311:101) Threshold V1 max
=
75.058 V
With the parameter
Threshold V1 max
, you can define the maximum threshold of the voltage band.
The setting value is closed to the allowed higher limit of the voltage band. The default setting is 130 % of the
rated positive-sequence voltage. The value of the rated positive-sequence voltage is 100 V/√3.
Parameter:
T Block
•
Default setting
(_:2311:6) T Block
=
0.10 s
With the parameter
T Block
, you set the dropout delay of the Δφ stage.
When voltages are connected or disconnected, the overfunction can be avoided with the timer
T Block
.
Siemens recommends to use the default setting of the parameter
T Block
. Keep in mind that the parameter
T Block
has always to be set to 2 cycles more than the measuring window for vector-jump measurement.
Settings
Addr.
Parameter
C
Setting Options
Default Setting
General
_:2311:102
General:Threshold V1
min
0.300 V to 175.000 V
46.189 V
_:2311:101
General:Threshold V1
max
0.300 V to 175.000 V
75.058 V
_:2311:6
General:T Block
0.00 s to 60.00 s
0.10 s
Information List
No.
Information
Data Class
(Type)
Type
General
_:2311:301
General:Δφ
MV
O
_:2311:300
General:Δφ out of meas. range
SPS
O
6.36.3.2
6.36.3.3
6.36.3.4
Protection and Automation Functions
6.36 Vector-Jump Protection
794
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Содержание 7SJ82
Страница 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...