[dwtime-dependent-110815-01.vsd, 1, en_US]
Parameter: Imax thermal
•
Recommended setting value
(_:107) Imax thermal
=
2.5 A
for l
rated
= 1 A
The
Imax thermal
parameter allows you to set the threshold current for the
Behav. at I> Imax
therm.
parameter. The selected current threshold of 2.5 I
rated, obj
is a practicable value.
Parameter: Temperature rise at Irated
•
Default setting
(_:109) Temperature rise at Irated
=
70 K
i
i
NOTE
For an application as a 1-phase overload protection, the ambient temperature measured via the tempera-
ture sensor is not taken into account. Therefore, the setting has no influence. You can keep the default
setting. If you take into account the temperature, note the following descriptions.
Set the overtemperature as the value that is the result if the equipment is continuously operated with the
rated current and at an ambient temperature of 40°C. Here, the rated current refers to the protected object.
You can find the temperature value in the Technical data of the equipment or you can measure the value. If
you use a temperature sensor when measuring at the rated current, deduct the actual ambient temperature or
the coolant temperature from the measured value.
When selecting the setting value, you can also use the specified temperature class for orientation. Usually, you
will find the overtemperature expressed in Kelvin (K), which can be accepted as is. If the absolute temperature
is given, the ambient temperature must be deducted. As a rule, this is 40 °C.
The overtemperature at maximum permissible current (
ϑmax
) and the
Temperature rise at Irated
(
ϑrated,obj.
) can be converted by using the following formula:
Protection and Automation Functions
6.21 Thermal Overload Protection, 1-Phase
682
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Содержание 7SJ82
Страница 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...