This information is needed in the following protection-related additional functions:
•
Trip logic (see
)
•
Detection of manual closing (see
)
•
Process monitor (Standard V/I)
Its use is described in the respective chapters.
The control does not use this information. The control evaluates the circuit-breaker auxiliary contacts.
[lozust3p-070611-01.tif, 1, en_US]
Figure 5-86
Overview of the Circuit-Breaker Condition Position Function
Based on the link between the information from the auxiliary contacts and the current flow, the circuit breaker
can assume the following positions:
Circuit-Breaker Condi-
tion
Description
Open
The circuit-breaker pole is detected unambiguously as open according to both
criteria.
Closed
The circuit-breaker pole is detected unambiguously as closed according to both
criteria.
Possibly open, possibly
closed
These conditions can occur if the information is incomplete due to the routing of
the auxiliary contacts and the condition can no longer be determined reliably.
These uncertain conditions are evaluated differently by certain functions.
Opening
This is a dynamically occurring condition that results when, while a trip command
is active and the auxiliary contact is still closed, the current is detected to have
fallen below the threshold value because the current-flow criterion takes effect
faster than the auxiliary contact can open.
Detection Manual Closure (for AREC and Process Monitor)
Function Description
Detection of Manual Closure (for AREC and Process Monitor)
The Manual closure function block detects any closure carried out by hand. This information is used in func-
tion, the automatic reclosing (AREC) and Process monitor functions (within protection function groups).
You can find detailed information in the chapters Automatic reclosing function and Process monitor.
The following figure shows the logic for manual closure detection.
5.7.9
5.7.9.1
Function-Group Types
5.7 Function-Group Type Circuit Breaker
SIPROTEC 5, Overcurrent Protection, Manual
291
C53000-G5040-C017-8, Edition 07.2017
Содержание 7SJ82
Страница 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...