Subsequent test time
During this second test time, the number of times a signal changes its status is checked once again. The
time begins when the
Chatter idle time
expires. If the number of status changes is within the
permissible limits, the signal is released. Otherwise, an additional dead time begins, unless the maximum
number of chatter tests has been reached.
Enter a number between 2 and 65535 in this field. The number entered corresponds to the time in
seconds. An entry here is only considered if the number of chatter tests does not equal 0.
Example 1: Permanent Blocking
The chatter-blocking settings are set as follows:
•
No. permis.state changes
= 4
•
No. of chatter tests
= 2
After more than 4 state changes within the
Initial test time
, the input signal is set to the original state
by the chatter blocking and the oscillatory quality is assigned. Additionally, a corresponding indication is
added to the operational log. At the same time, the
Chatter blocking
indication is set. After expiry of the
settable
Chatter idle time
, during the following
Subsequent test time
, it is checked whether the
input signal is still chattering. This check is repeated, as the
No. of chatter tests
is set to 2 in this
example.
If, during the 2nd
Subsequent test time
, it has been detected that the number of status changes of the
input signal exceeds the set
No. permis.state changes
, the chatter blocking detects a persistent viola-
tion of the signal stability and sets the
Group warning
indication. The original state of the signal is perma-
nently frozen. Only a device restart removes the chatter blocking again.
[dw_chatter-block-01, 1, en_US]
Figure 3-81
Signal Change during Chatter Blocking with too Important Number of Signal State Changes
During 2nd Subsequent Test Time
(1)
The input signal is permanently blocked starting from this point in time.
System Functions
3.8 Other Functions
SIPROTEC 5, Overcurrent Protection, Manual
163
C53000-G5040-C017-8, Edition 07.2017
Содержание 7SJ82
Страница 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...