With the
Rated secondary current
parameter, you set the current rated secondary current of the current
transformer.
Parameter: Current range
•
Default setting 7SJ82
(_:8881:117) Current range
=
50 x IR
•
Default setting 7SJ85
(_:8881:117) Current range
=
100 x IR
The
Current range
parameter allows you to set the dynamic range for the current input. Please retain the
default setting for power-system protection applications. The current measuring range 1.6 x Irated applies for
the connection type
3-phase + IN-separate
and the sensitive current input or for the measuring inputs.
Parameter: Neutr.point in dir.of ref.obj
•
Default setting
(_:8881:116) Neutr.point in dir.of ref.obj
=
yes
The
Neutr.point in dir.of ref.obj
parameter is used to set the direction of the neutral point of the
current transformer (see following figure). Often, the neutral point of the current transformer is determined
by the direction of the protected object (for example, in the direction of the line, cable, transformer). For this
reason, the default setting of the parameter was defined as
yes
.
When switching the parameter, the direction of the phase currents and of the ground current IN or IN-sepa-
rate is rotated device-internally.
[dwpolstromwdl-251013, 1, en_US]
Figure 6-2
Polarity of Current Transformers
Parameter: Inverted phases
•
Default setting
(_:8881:114) Inverted phases
=
none
The
Inverted phases
parameter is intended for special applications, for example, pumped-storage hydro-
power plants (see Chapter Phase-rotation reversal). This default setting may be retained for power-system
protection applications.
Parameter: Magnitude correction
•
Default setting
(_:3841:103) Magnitude correction
=
1.000
When using the
Magnitude correction
parameter, you adjust the magnitude (magnitude correction) for
the current input. This allows you to correct the tolerances of the primary current transformer phase-selec-
tively. The magnitude correction may be required for highly precise measurements. Use a comparison meas-
urement to determine the setting value (for example, with a high-precision measuring-voltage transformer). If
a primary correction is not necessary, retain the default setting.
Protection and Automation Functions
6.1 Power-System Data
SIPROTEC 5, Overcurrent Protection, Manual
305
C53000-G5040-C017-8, Edition 07.2017
Содержание 7SJ82
Страница 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...