![Siemens 7SJ82 Скачать руководство пользователя страница 1271](http://html.mh-extra.com/html/siemens/7sj82/7sj82_manual_3826421271.webp)
No.
Information
Data Class
(Type)
Type
_:2311:501
General:>MP-ID selection
INS
I
_:2311:54
General:Inactive
SPS
O
_:2311:52
General:Behavior
ENS
O
_:2311:53
General:Health
ENS
O
_:2311:307
General:Main-voltage failure
ACD
O
_:2311:308
General:Ref.-voltage failure
ACD
O
_:2311:309
General:Selection invalid
SPS
O
Broken-Wire Detection
Overview of Functions
The purpose of the broken-wire detection is to detect interruptions in the secondary circuit of the current
transformers during steady-state operation.
Structure of the Function
The Broken-wire detection function is located in the power-system data of each 3-phase current measuring
point.
[dwbwsjsk-301112-01.tif, 2, en_US]
Figure 9-23
Structure/Embedding of the Function
The tasks of Broken-wire detection are:
•
The instantaneous values of all current measuring points are checked on a phase-selective basis for
implausible values.
•
The affected phases are marked with wire-break suspected.
•
Depending on the supervision mode, you can add a marker for blocking protection functions for the
affected phases.
•
After 10 ms of broken-wire check, the wire break is reliably signaled.
Function Description
Broken Wire Suspected
The Broken-wire detection function monitors the dynamic behavior of the currents of each phase and of all
measuring points. For this purpose, the instantaneous values of the currents are checked for their plausibility.
Each expected violation must be confirmed by additional criteria before a wire break can be detected and
signaled with assurance.
The detection of the local broken wire suspected is performed on each 3-phase current measuring point of the
device selectively for each phase.
Detection:
A wire break initially manifests itself as a sudden decrease of the current below the minimum threshold of
0.06 I/I
rated.
A plausibility test on one period of past instantaneous values confirms this condition. If the criteria
for the local wire break are satisfied, the affected phase is marked with Broken wire suspected.
9.3.9
9.3.9.1
9.3.9.2
9.3.9.3
Supervision Functions
9.3 Supervision of the Secondary System
SIPROTEC 5, Overcurrent Protection, Manual
1271
C53000-G5040-C017-8, Edition 07.2017
Содержание 7SJ82
Страница 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...