These parameters are used to define the direction characteristic of the stage. The direction characteristic to
use is dependent on the neutral-point treatment of the system.
Note that, for the direction determination, basically only the component of the admittance perpendicular to
the set direction-characteristic curve is decisive, see chapter
. This admittance component
is compared to the threshold value
Polarized G0/B0 threshold
. In contrast, the absolute value of the
current 3I0 is compared with the
3I0> release thresh. value
parameter.
System Type/
Neutral-Point Treat-
ment
Description
Grounded
In the arc-suppression-coil-ground system, the watt-metric residual current 3I0 · cos φ
of the arc-suppression coil is decisive for the direction determination.
To evaluate the watt-metric residual current, set the parameters as follows:
•
Dir. measuring method
=
G0
•
φ correction
=
0.0°
The direction determination for a ground fault is made more difficult in that a much
larger reactive current of capacitive or inductive character is superimposed on the small
watt-metric residual current. Therefore, depending on the system configuration and
the fault evaluation, the total ground current supplied to the device can vary consider-
ably in its values regarding the magnitude and the phase angle. However, the device
should only evaluate the active component of the ground-fault current.
This requires extremely high accuracy, particularly regarding the phase-angle measure-
ment of all the instrument transformers. Furthermore, the device must not be set to
operate too sensitively. A reliable direction measurement can only be expected with
connection to a core balance current transformer. For the setting of the
Polarized
G0/B0 threshold
parameter, the following formula applies:
where:
k
s
: Safety margin, k
s
= 1.2 (cable networks), k
s
= 2.0 (overhead lines)
I
0active
: Active component of the ground-fault current (watt-metric residual current) of
the protected line
V
rated
: Secondary rated voltage in the healthy case
I
0min
: Min. ground current in the healthy case, 5 mA to 10 mA (core balance current
transformer), 50 mA to 100 mA (Holmgreen transformer)
V0>: Pickup threshold of the residual voltage ≈ 0.1
If a parallel resistor Rp is used on the arc-suppression coil, the threshold value G0 must
also be smaller than:
where:
k
s
: Safety margin ≥ 1.5
I
Rp
: Secondary rated current of the parallel resistor
V
rated
: Secondary rated voltage in the healthy case
The
3I0> release thresh. value
parameter can be set to half of the expected
measuring current and here, the entire zero-sequence current can be put to use.
Protection and Automation Functions
6.15 Sensitive Ground-Fault Detection
SIPROTEC 5, Overcurrent Protection, Manual
597
C53000-G5040-C017-8, Edition 07.2017
Содержание 7SJ82
Страница 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...