Table 8-28
Possible Fundamental Values for the Voltage Controller Function Group
Fundamental-Component Values
Primar
y
Secon-
dary
% Referenced to
I
A
, I
B
, I
C
Phase currents
A
A
Rated operating current of the
primary system
I
N
Measured zero-sequence current
A
A
Rated operating current of the
primary system
V
A
, V
B
, V
C
Phase-to-ground voltages
kV
V
Rated operating voltage of the
primary system/√3
V
AB
, V
BC
, V
CA
Phase-to-phase voltages
kV
V
Rated operating voltage of the
primary system
V
N
Measured neutral-point displace-
ment voltage
kV
V
Rated operating voltage of the
primary system/√3
Table 8-29
Possible Power Measured Values of the Voltage Controller Function Group
Power Measured Value
Primar
y
Secon-
dary
% Referenced to
P
total
Active power
(total power)
MW
W
Active power of the primary system
√3 ⋅ V
rated
⋅ I
rated
Q
total
Reactive power
(total power)
Mvar
var
Reactive power of the primary system
√3 ⋅ V
rated
⋅ I
rated
S
total
Apparent power
(total power)
MVA
VA
Apparent power of the primary
system
√3 ⋅ V
rated
⋅ I
rated
Cos φ
Active power factor
(abs)
(abs)
100 % corresponds to cos φ = 1
Application and Setting Notes Voltage Controllers
Two-Winding Transformer: General
Parameter: Rated current
•
Default setting
(_:2311:101) Rated current
=
1000.00 A
Parameter: Rated voltage
•
Default setting
(_:2311:102) Rated voltage
=
400.00 kV
The measured values of the voltage controller can be displayed as primary values, secondary values, or in
percent. With the
Rated current
and
Rated voltage
parameters, you set the reference value for the
percentage values.
Three-Winding Transformer and Grid Coupling Transformer: General
Winding 1
Parameter: Rated current
•
Default setting
(_:2311:101) Rated current
=
1000.00 A
Parameter: Rated voltage
•
Default setting
(_:2311:103) Rated voltage
=
400.00 kV
Winding 2
Parameter: Rated current
•
Default setting
(_:2311:102) Rated current
=
1000.00 A
8.9.4
Control Functions
8.9 Voltage Controller
1212
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Содержание 7SJ82
Страница 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...