No.
Information
Data Class
(Type)
Type
_:5071:317
Synchrocheck 1:V dif.too large(V2>V1)
SPS
O
_:5071:318
Synchrocheck 1:V dif.too large(V2<V1)
SPS
O
_:5071:319
Synchrocheck 1:f dif.too large(f2>f1)
SPS
O
_:5071:320
Synchrocheck 1:f dif.too large(f2<f1)
SPS
O
_:5071:329
Synchrocheck 1:dfdiff/dt too large
SPS
O
_:5071:321
Synchrocheck 1:α dif.too large(α2>α1)
SPS
O
_:5071:322
Synchrocheck 1:α dif.too large(α2<α1)
SPS
O
_:5071:304
Synchrocheck 1:Max. time exceeded
SPS
O
_:5071:323
Synchrocheck 1:Setting error
SPS
O
Stage Synchronous/Asynchronous
Description
A distinction according to synchronous and asynchronous systems can be made with this type of stage.
If galvanically coupled systems are switched in parallel, synchronous systems are present. A typical character-
istic for synchronous systems is equality of frequency (Δf ≈ 0). If the frequency difference falls below the
setting value of the
f-threshold ASYN<->SYN
parameter, synchronous systems are to be assumed. If the
frequency difference exceeds the setting value of the
f-threshold ASYN<->SYN
parameter, asynchronous
systems are to be assumed. This status occurs in galvanically isolated systems, for example.
Both states have their own operating mode with its own closing conditions. Both operating modes can be
switched on and off separately (parameter
Sync. operating mode
and
Async. operating mode
). The
following combinations result from this:
Sync. operating mode Async. operating
mode
Functionality
on
on
If the frequency difference is below the threshold
value set
f-threshold ASYN<->SYN
the oper-
ating mode synchronous is active. In other cases,
the operating mode asynchronous is active.
off
on
Regardless of the frequency difference and the
threshold value
f-threshold ASYN<->SYN
the
operating mode is exclusively active asynchro-
nously.
on
off
If the frequency difference is below the threshold
value set
f-threshold ASYN<->SYN
, the oper-
ating mode synchronous is active. In other cases,
the stage is inactive, i.e. a switching release
cannot be issued.
off
off
Both operating modes are deactivated. No activa-
tion release can be be given via these operating
modes either.
8.4.8
8.4.8.1
Control Functions
8.4 Synchronization Function
SIPROTEC 5, Overcurrent Protection, Manual
1145
C53000-G5040-C017-8, Edition 07.2017
Содержание 7SJ82
Страница 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...