Manually set the desired distance for “Q
1
far”
Operating example or steps:
RUN mode
→ Q
1
Output
→ ModeQ
1
/
to → Manual Q
1
→ Q
1
near
/
to → Q
1
far
→
3
0000 (Note:
3
= flashing 3)
/
,
/
,
/
,
/
,
/
→ desired distance in mm
→ Saved
to → RUN mode
Necessary default settings:
Mode Q
1
= Window
Factory setting:
-
Manually switch the logic for Q
1
to “Low Active”
Operating example or steps:
RUN mode
→ Q
1
Output
→ ModeQ
1
/
to → Manual Q
1
→ Q
1
near
/
to → Q
1
Logic
→ High Active
/
to → Low Active
→ Saved
to → RUN mode
Necessary default settings:
Mode Q
1
= Window
Factory setting:
High Active
For the output function Q
2
configure and activate /Q
a
through switching
Operating example or steps:
RUN mode
→ Q
1
Output
/
to → Q
2
Output
→ Function Q
2
/Q
a
→ 4 - 20 mA
/
to → Switching
→ Saved
to → RUN mode
Necessary default settings:
-
Factory setting:
4 - 20 mA
6
OPERATION
30
O P E R A T I N G I N S T R U C T I O N S | DT50-2 Pro
8017154/1AVV/2021-03-24 | SICK
Subject to change without notice