5
Electrical installation
Installation instructions (all versions)
Operating Instructions – MOVIFIT
®
FC
56
Ambient temperature
MOVIFIT
®
FC (except model rated 4 kW) is suitable for an ambient temperature of
40 °C, max. 60 °C with derated output current. To determine the output current rating
at higher than 40 °C, the output current should be derated 3.0% per °C between 40 °C
and 60 °C.
MOVIFIT
®
FC (model rated 4 kW) is suitable for an ambient temperature of 35 °C,
max. 55 °C with derated output current. To determine the output current rating at high-
er than 35 °C, the output current should be derated 3.0% per °C between 35 °C and
55 °C.
ABOX-EBOX combination
For UL-compliant installation, only the EBOX specified on the ABOX nameplate may
be mounted to the ABOX. The UL certification refers only to the ABOX/EBOX combi-
nation stated on the nameplate.
The UL certification only applies for operation on voltage supply systems with voltages
to ground of max. 300 V. UL approval does not apply for operation on voltage supply
systems with a non-grounded star point (IT systems).
21316996/EN – 12/2014
Содержание MOVIFIT FC