7
Operation
Status LEDs MOVIFIT® FC
Operating Instructions – MOVIFIT
®
FC
160
LED
Meaning
Operating state
error code
Possible cause
Red
Flashing
twice,
pause
Fault 07
DC link voltage too high.
Red
Flashing
slowly
Fault 08
Speed monitoring error
Fault 09
Incorrect startup/parameterization.
Fault 15
24 V supply voltage too low.
Faults 17 – 24, 37
CPU error
Fault 25
EEPROM error
Fault 26
Fault at external terminal (only at slave unit)
Error 38, 45
Unit/motor data error
Fault 90
Incorrect motor/inverter assignment.
Invalid DIP switch setting.
Fault 94
Checksum error
Fault 97
Copy error
Red
Flashing 3
times,
pause
Fault 01
Overcurrent in output stage
Fault 11
Overtemperature in output stage
Red
Flashing 4
times,
pause
Fault 31
Temperature sensor tripped.
Fault 84
Motor overload
Red
Flashing 5
times,
pause
Fault 4
Overcurrent in brake chopper
Fault 89
Brake overtemperature
Incorrect motor/frequency inverter assignment.
Red
Flashing 6
times,
pause
Fault 06
Line phase failure
Fault 81
Start condition (only in hoist operation mode)
Fault 82
Open output.