9
Technical data
Interfaces
Operating Instructions – MOVIFIT
®
FC
186
DeviceNet™ interface
DeviceNet™
Function level
Classic
Technology
Protocol variant
Master-slave connection set with polled I/O and bit-strobe I/O
Supported baud rates
500 kBd
250 kBd
125 kBd
Cable length DeviceNet™
See DeviceNet™ specification V 2.0
500 kBd 100 m
250 kBd 250 m
125 kBd 500 m
Bus termination
120 Ω (switch on externally)
Process data configuration
See "MOVIFIT
®
Function Level
Classic..." manual
See "MOVIFIT
®
Function Level
Technology.." manual
Bit-strobe response
Checkback signal of the unit status via bit-strobe I/O data
Address setting
DIP switch
Name of EDS files
SEW_MOVIFIT_Classic.eds
SEW_MOVIFIT_TECH_DNET.eds
Name of icon files
SEW_MOVIFIT_Classic.ico
SEW_MOVIFIT_TECH_DNET.ico
21316996/EN – 12/2014
Содержание MOVIFIT FC
Страница 2: ...SEW EURODRIVE Driving the world ...
Страница 225: ......
Страница 226: ......
Страница 227: ......