Assigning the slave address using a hand-held programming device
Hand-held AS-Interface programming devices offer the following functions:
•
Reading and changing an AS-Interface slave address
•
Reading the AS-Interface profile
•
Reading and changing the data and parameter bits
•
Function check and test run.
Hand-held programming devices do not provide sufficient current for the operation.
This is why an external voltage supply (AUX-PWR) is required for the function
check and the test run.
When using a hand-held programming device, you need a
2-core
connection cable
that fits onto the AS-Interface plug connector on MOVIMOT
®
(see the following figure).
4
2
1
3
1:
2:
3:
4:
AS-Int
0V24 [1]
AS-Interface -
24V
[1]
1127256715
[1]
Do not connect pin 2 and 4 for the address assignment!
NOTICE:
The hand-held programming device can be damaged if not connected pro-
perly.
•
The hand-held programming device may
only
be connected via pins 1 "AS-Inter-
face +" and 3 "AS-Interface -" with the AS-Interface plug connector.
•
Prior to the address assignment via a hand-held programming device, switch S5 in
the MOVIMOT
®
connection box must be set to "1".
•
After the address assignment you must set switch S5 according to the type of 24 V
voltage supply.
Example:
Disconnect the AS-Interface nodes from the AS-Interface network
one at a time
and
assign addresses via the hand-held programming device (A).
Reconnect the respective AS-Interface node to the AS-Interface network (B).
A
B
MOVIMOT
[1]
9007200382410891
[1]
AS-Interface hand-held programming device
27792307/EN – 07/2022