4 INSTALLATION AND INITIAL SETUP
4.1
Quick Installation Guide
1. Read the safety instructions, refer to chapter 3
2. Install the unit in a 19 inch rack for rack mount probes, refer to section 4.6
3. Connect the signal cables, refer to section 4.5
4. Power up the unit, refer to section 4.7
5. Perform initial set-up of IP addresses, refer to section 4.8
6. Verify that the GUI launches correctly, refer to section 4.8.3
4.2
The Enhanced Chassis (VB300)
The 1RU Enhanced Chassis can house a maximum of
2
modules, and it is equipped with two 100–240V
AC 75W power supplies. The unit is forced air ventilated, the air flow going from front to back. The
maximum power consumption of the chassis with optional modules is 75W. By default all connectors are
located at the front of the unit. The power plugs are located at the rear of the unit. The rack ears of the
chassis may be moved to provide for mid or rear mounting of the unit. The rack ears are designed to
support the weight of the unit.
Figure 4.1: The Enhanced Chassis with probe boards installed
VB3xx 10G Probe User’s Manual version 5.3
15