27
26
Voltage
decline time
of V/F
separation
0.0s
〜
1000.0s
Note
:
Indicates the time from
0V changes to the rated
voltage of the motor
0.0s
V/F Separate
shutdown
mode
selection
0
50~200%
150%
Over-current
suppression
0
:
Invalid
1
: Valid
1
Over current
stall gain
0~100
20
Double
speed overrun
speed action
current
compensation
coefficient
50~200%
50%
Overvoltage
stall
operating
voltage
200.0V~2000.0V
0
:
Invalid
1
:
Valid
1
Overvoltage
stall
suppression
frequency
gain
0~100
30
Overvoltage
stall
suppression
voltage gain
Overvoltage
stall
maximum
rising
frequency
limit
0~50Hz
5Hz
Slip
compensation
time constant
0.1~10.0s
0.5
Function
Code
Parameter
Name
Setting Range
Default
Prope-
rty
Modbus
Address
P3-16
○
P3-17
○
0 : frequency / voltage is
independently reduced to 0
1 : After the voltage is reduced
to 0, the frequency is reduced
again.
Overcurrent
stall
operating
current
P3-18
●
P3-19
●
P3-20
○
P3-21
●
P3-22
●
Model
dependent
220V:380V
380V:760V
480V:850V
Overvoltage
stall enable
P3-23
●
P3-24
●
0~100
30
P3-25
●
P3-26
●
P3-27
Fun-
ction
Code
Parameter
Name
Setting range
Default
Prope-
rty
Modbus
Address
○
P4: Multi functional inputs parameters
P4-00
Fun-
ction
Code
Parameter
Name
Setting range
Default
Prope-
rty
Modbus
Address
X1 Terminal
function
selection
1
4
9
●
P4-01
X2 Terminal
function
selection
●
P4-02
X3 Terminal
function
selection
●
12
P4-03
X4 Terminal
function
selection
●
User Manual
Chapter 5
User Manual
Chapter 5
P3-34
Water supply
mode
selection
0: Turn off water supply mode
1: Turn on the water supply mode
0
P3-35
Remote
transmission
of pressure
gauge range
0.00
〜
5.00MPa
1.00MPa
P3-36 Demand target
pressure
0.00~P3-39
0.5MPa
P3-37
Dormancy
frequency
0.00 Hz~P0-10
25.00Hz
P3-38 Sleep latency 0.0~3600.0s
0.0s
P3-39
Wake up the
pressure
0.0~100.0%
80%
P3-40
Wake up time
delay
0.0~3600.0s
0.0s
●
○
0 : No function
1 : Forward RUN (FWD)
2 : Reverse RUN (REV)
3 : Three-line control
4 : Forward JOG (FJOG)
5 : Reverse JOG (RJOG)
6 : Terminal UP
7 : Terminal DOWN
8 : Coast to stop
9 : Fault reset (RESET)
10 : RUN pause
11 : Normally open (NO) input of
external fault
12: Multi-speed 1
13: Multi-speed 2
14: Multi-speed 3
15: Multi-speed 4
16 : Acceleration/deceleration
time selection 1
○
○
○
○
○
62225
62226
62227
62228
62229
62230
62231
62232
62233
62234
62235
62236
62243
62244
62245
62246
62247
62248
62249
62465
62466
62467
62468