41
40
P8-31
0.0%
〜
100.0%
(Maximum frequency)
0.0%
P8-32
0.00Hz
〜
Maximum frequency
50.00Hz
P8-33
0.0%
P8-34
Zero current
detection level
0.0%
〜
300.0%
100.0% Corresponding motor
rated current
5.0%
P8-35
Zero current
detection
delay time
0.01s
〜
600.00s
0.10s
P8-36
Output
overcurrent
threshold
200.0%
P8-37
Output
overcurrent
detection
delay time
0.00s
〜
600.00s
0.00s
P8-38
Arbitrary
arrival current 1
0.0%
〜
300.0%
(Motor rated current
)
100.0%
P8-39
Arbitrary
current 1 width
0.0%
〜
300.0%
(
Motor rated current
)
0.0%
P8-40
Arbitrary
arrival current 2
0.0%
〜
300.0%
Motor rated current
)
100.0%
P8-41
Arbitrary
current 2 width
0.0%
〜
300.0%
(Motor rated current)
0.0%
P8-42
Timing
function
0 : Invalid
1 : Valid
0
●
P8-43
Timing
duration
source
0
P8-44
Timing
duration
0.0Min
〜
6500.0Min
0.0Min
P8-45
AI1 input
voltage pro-
tection value
lower limit
0.00V
〜
P8-46
3.10V
P8-46
AI1 input
voltage pro-
tection value
upper limit
P8-45
〜
10.00V
6.80V
P8-47
IGBT
temperature
threshold
0
℃〜
100
℃
75
℃
P8-48
Cooling fan
control
0
P8-49
Wake-up
frequency
Dormant frequency
(P8-51)
〜
Maximum frequency (P0-10)
0.00Hz
P8-50
Wake-up
delay time
0.0s
〜
6500.0s
0.0s
P8-51
Dormant
frequency
0.00Hz
〜
Wake-up frequency
(
P8-49
)
0.00Hz
P8-52
Dormant
delay time
0.0s
〜
6500.0s
0.0s
P8-53
Current
running time
reached
0.0Min
〜
6500.0Min
0.0Min
●
P8-54
Output power
correction
coefficient
0.00%
〜
200.0%
100.0%
Parameter
Name
Setting Range
Default
Prope-
rty
Modbus
Address
○
Fun-
ction
Code
Arbitrary arri-
val frequency
detection
width 1
○
Arbitrary arri-
val frequency
detection
value 2
○
0.0%
〜
100.0%
(Maximum frequency)
Arbitrary arri-
val frequency
detection
width 2
○
○
○
0.0%(Not detecting)
0.1%~300.0%
(Motor rated current)
○
○
○
○
○
●
0 : P8-44 setting 1 : AI1
2 : AI2 3 : AI3
Analog input range
corresponding P8-44
●
○
Fun-
ction
Code
Parameter
Name
Setting range
Default
Prope-
rty
Modbus
Address
○
0 : The fan is running during
operation
1 : The fan is always running
○
○
○
○
○
○
○
P9: Failure and protection
Fun-
ction
Code
Parameter
Name
Setting range
Default
Prope-
rty
Modbus
Address
P9-00
Motor overload
protection
selection
0 : Not allow
1 : Allow
1
P9-01
Motor overload
protection gain
0.20
〜
10.00
1.00
P9-02
Motor overload
warning
coefficient
50%
〜
100%
80%
P9-03
Overvoltage
stall gain
0 (no stall overvoltage)–100
30
P9-04
Overvoltage
stall protective
voltage
65V~800V
760V
○
User Manual
Chapter 5
User Manual
Chapter 5
○
○
○
○
63520
63521
63522
63523
63524
63525
63526
63527
63528
63529
63530
63531
63532
63533
63534
63535
63536
63537
63538
63539
63540
63541
63542
63543
63745
63746
63747
63748
63749