6-2
Close and Reclose Logic
Date Code 20011205
SEL-311B Instruction Manual
See the settings sheet in
Section 9: Setting the Relay
for setting ranges.
From Figure 6.2
Figure 6.1: Close Logic
Set Close
If all the following are true:
·
The unlatch close condition is not asserted (ULCL = logical 0).
·
The circuit breaker is open (52A = logical 0).
·
The reclose initiation condition (79RI) is not making a rising edge (logical 0 to
logical 1) transition.
·
And a close failure condition does not exist (Relay Word bit CF = 0).
Then the CLOSE Relay Word bit can be asserted to logical 1 if either of the following occurs:
·
A reclosing relay open interval times out (qualified by SEL
OGIC
control equation setting
·
Or SEL
OGIC
control equation setting CL goes from logical 0 to logical 1 (rising edge
transition).
The CLOSE command is included in the close logic in the factory settings:
CL = … + CC
Relay Word bit CC asserts for execution of the CLOSE Command. See
CLO Command (Close
Breaker)
in
Section 10: Serial Port Communications and Commands
for more information on
the CLOSE Command. More discussion follows later on the factory settings for setting CL.
Содержание SEL-311B
Страница 6: ......
Страница 8: ......
Страница 10: ......
Страница 24: ......
Страница 26: ......
Страница 122: ......
Страница 124: ......
Страница 138: ......
Страница 168: ......
Страница 172: ......
Страница 254: ......
Страница 282: ......
Страница 306: ......
Страница 348: ......
Страница 364: ......
Страница 366: ......
Страница 448: ......
Страница 460: ......
Страница 466: ......
Страница 476: ......
Страница 482: ......
Страница 494: ......
Страница 500: ......
Страница 522: ......
Страница 526: ......
Страница 528: ......
Страница 534: ......
Страница 536: ......
Страница 550: ......
Страница 570: ......
Страница 586: ......
Страница 600: ......