7-4
Inputs, Outputs, Timers, and Other Control Logic
Date Code 20011205
SEL-311B Instruction Manual
Input IN102
Relay Word bit IN102 (Figure 7.2) is used in the settings for the SEL
OGIC
control equation
drive-to-lockout setting:
79DTL = !IN102 + ...
[=NOT(IN102) + ...]
Connect input IN102 to a reclose enable switch.
When the reclose enable switch is open, input IN102 is deenergized and the reclosing relay is
driven to lockout:
79DTL = !IN102 + ... = NOT(IN102) + ... = NOT(logical 0) +... = logical 1
When the reclose enable switch is closed, input IN102 is energized and the reclosing relay is
enabled, if no other setting condition is driving the reclosing relay to lockout:
79DTL = !IN102 + ... = NOT(IN102) + ... = NOT(logical 1) +... = logical 0 + ...
See
Section 6: Close and Reclose Logic
for more information on SEL
OGIC
control equation
setting 79DTL.
The pickup/dropout timer for input IN102 (IN102D) in this example might be set at:
IN102D = 1.00 cycle
to provide input energization/deenergization debounce.
Содержание SEL-311B
Страница 6: ......
Страница 8: ......
Страница 10: ......
Страница 24: ......
Страница 26: ......
Страница 122: ......
Страница 124: ......
Страница 138: ......
Страница 168: ......
Страница 172: ......
Страница 254: ......
Страница 282: ......
Страница 306: ......
Страница 348: ......
Страница 364: ......
Страница 366: ......
Страница 448: ......
Страница 460: ......
Страница 466: ......
Страница 476: ......
Страница 482: ......
Страница 494: ......
Страница 500: ......
Страница 522: ......
Страница 526: ......
Страница 528: ......
Страница 534: ......
Страница 536: ......
Страница 550: ......
Страница 570: ......
Страница 586: ......
Страница 600: ......