Setting the Relay
Date Code 20011205
SEL----311B Instruction Manual
RID and TID settings may include the following characters: 0–9, A–Z, #, &, @, -, /, ., space.
These two settings cannot be made via the front-panel interface.
Current Transformer Ratios
Refer to Settings Sheet 1.
Phase and polarizing current transformer ratios are set independently.
Line Settings
Refer to Settings Sheet 1.
Line impedance settings Z1MAG, Z1ANG, Z0MAG, and Z0ANG are used in distance relaying,
fault locator (see
Fault Location
in
Section 12: Standard Event Reports and SER
) and in
automatically making directional element settings Z2F, Z2R, Z0F, and Z0R (see
Settings Made
Automatically
in
Section 4: Loss-of-Potential Logic, CCVT Transient Detection,
Load-Encroachment, and Directional Element Logic
). A corresponding line length setting (LL)
is also used in the fault locator.
The line impedance settings Z1MAG, Z1ANG, Z0MAG, and Z0ANG are set in
W
secondary. To
convert line impedance (
W
primary) to
W
secondary:
W
primary • (CTR/PTR) =
W
secondary
where:
CTR = phase (IA, IB, IC) current transformer ratio
PTR = phase (VA, VB, VC) potential transformer ratio (wye-connected)
Line length setting LL is unitless and corresponds to the line impedance settings. For example, if
a particular line length is 15 miles, enter the line impedance values (
W
secondary) and then enter
the corresponding line length:
LL
=
15.00
(miles)
If the same length of line is measured in kilometers rather than miles, then enter:
LL
=
24.14
(kilometers)
Enable Settings
Refer to Settings Sheets 1, 2, and 17.
The enable settings on Settings Sheets 1 and 2 (E21P through EADVS) control the settings that
follow, through Sheet 10. Enable setting, EBMON, on Settings Sheet 17 controls the settings that
immediately follow it. This helps limit the number of settings that need to be made.
Each setting subgroup on Settings Sheets 2 through 10 has a reference back to the controlling
enable setting. For example, the residual time-overcurrent element settings on Sheet 5 (settings
51GP through 51GRS) are controlled by enable setting E51G.
Содержание SEL-311B
Страница 6: ......
Страница 8: ......
Страница 10: ......
Страница 24: ......
Страница 26: ......
Страница 122: ......
Страница 124: ......
Страница 138: ......
Страница 168: ......
Страница 172: ......
Страница 254: ......
Страница 282: ......
Страница 306: ......
Страница 348: ......
Страница 364: ......
Страница 366: ......
Страница 448: ......
Страница 460: ......
Страница 466: ......
Страница 476: ......
Страница 482: ......
Страница 494: ......
Страница 500: ......
Страница 522: ......
Страница 526: ......
Страница 528: ......
Страница 534: ......
Страница 536: ......
Страница 550: ......
Страница 570: ......
Страница 586: ......
Страница 600: ......