7-38
Inputs, Outputs, Timers, and Other Control Logic
Date Code 20011205
SEL-311B Instruction Manual
Make corresponding, complementary text settings:
DP1_1 = 79 ENABLED
DP1_0 = 79 DISABLED
Display point setting DP1 controls the display of the text settings.
Reclosing Relay Enabled
In Figure
7.28, optoisolated input IN102 is energized to enable the reclosing relay, resulting in:
DP1
= IN102 = logical 1
This results in the display of corresponding text setting DP1_1 on the front-panel display:
79 ENABLED
Reclosing Relay Disabled
In Figure
7.28, optoisolated input IN102 is deenergized to disable the reclosing relay, resulting
in:
DP1
= IN102 = logical 0
This results in the display of corresponding text setting DP1_0 on the front-panel display:
79 DISABLED
Circuit Breaker Status Indication
Make SEL
OGIC
control equation display point setting DP2:
DP2 =
IN101
Make corresponding, complementary text settings:
DP2_1 = BREAKER CLOSED
DP2_0 = BREAKER OPEN
Display point setting DP2 controls the display of the text settings.
Содержание SEL-311B
Страница 6: ......
Страница 8: ......
Страница 10: ......
Страница 24: ......
Страница 26: ......
Страница 122: ......
Страница 124: ......
Страница 138: ......
Страница 168: ......
Страница 172: ......
Страница 254: ......
Страница 282: ......
Страница 306: ......
Страница 348: ......
Страница 364: ......
Страница 366: ......
Страница 448: ......
Страница 460: ......
Страница 466: ......
Страница 476: ......
Страница 482: ......
Страница 494: ......
Страница 500: ......
Страница 522: ......
Страница 526: ......
Страница 528: ......
Страница 534: ......
Страница 536: ......
Страница 550: ......
Страница 570: ......
Страница 586: ......
Страница 600: ......