7-10
Inputs, Outputs, Timers, and Other Control Logic
Date Code 20011205
SEL-311B Instruction Manual
If settings are changed for a setting group other than the active setting group, there is no
interruption of the local bits (the relay is not momentarily disabled).
If a local control switch is made inoperable because of a settings change (i.e., the corresponding
label settings are nulled), the corresponding local bit is then fixed at logical 0, regardless of the
local bit state before the settings change. If a local control switch is made newly operable
because of a settings change (i.e., the corresponding label settings are set), the corresponding
local bit starts out at logical 0.
R
EMOTE
C
ONTROL
S
WITCHES
Remote control switches are operated via the serial communications port only (see
CON
Command (Control Remote Bit)
in
Section 10: Serial Port Communications and Commands
).
Figure 7.9: Remote Control Switches Drive Remote Bits RB1 Through RB16
The outputs of the remote control switches in Figure 7.9 are Relay Word bits RB
n
(
n
= 1 to 16),
called remote bits. Use these remote bits in SEL
OGIC
control equations.
Any given remote control switch can be put in one of the following three positions:
ON (logical
1)
OFF (logical
0)
MOMENTARY (logical 1 for one processing interval)
Содержание SEL-311B
Страница 6: ......
Страница 8: ......
Страница 10: ......
Страница 24: ......
Страница 26: ......
Страница 122: ......
Страница 124: ......
Страница 138: ......
Страница 168: ......
Страница 172: ......
Страница 254: ......
Страница 282: ......
Страница 306: ......
Страница 348: ......
Страница 364: ......
Страница 366: ......
Страница 448: ......
Страница 460: ......
Страница 466: ......
Страница 476: ......
Страница 482: ......
Страница 494: ......
Страница 500: ......
Страница 522: ......
Страница 526: ......
Страница 528: ......
Страница 534: ......
Страница 536: ......
Страница 550: ......
Страница 570: ......
Страница 586: ......
Страница 600: ......