4-22
Loss-of-Potential, CCVT Transient Detection,
Date Code 20011205
Load-Encroachment, and Directional Element Logic
SEL-311B Instruction Manual
From Figure 4.3
To Figure 3.4 through Figure 3.6
From Figure 4.1
Figure 4.15: Positive-Sequence Voltage-Polarized Directional Element for Phase Distance
Elements
D
IRECTIONAL
C
ONTROL
S
ETTINGS
The directional control for overcurrent elements is configured by making directional control
enable setting E32. Setting E32 has setting choices:
Y
All directional control settings made manually
AUTO Sets most of the directional element settings automatically
Settings Made Automatically
If the directional control enable setting E32 is set:
E32 = AUTO
then the following directional control settings are calculated and set automatically:
Z2F, Z2R, 50QFP, 50QRP, a2, k2, 50GFP, 50GRP, a0, Z0F, and Z0R