Date Code 20011205
Loss-of-Potential, CCVT Transient Detection,
4-5
Load-Encroachment, and Directional Element Logic
SEL-311B Instruction Manual
Figure 4.3: Load-Encroachment Logic With Example Settings
A positive-sequence impedance calculation (Z
1
) is made in the load-encroachment logic in Figure
4.3. Load is largely a balanced condition, so apparent positive-sequence impedance is a good
load measure. The load-encroachment logic only operates if the positive-sequence current (I
1
) is
greater than the Positive-Sequence Threshold shown in Figure 4.3. For a balanced load
condition, I
1
= phase current magnitude.
Forward load (load flowing out) lies within the hatched region labeled ZLOUT. Relay Word bit
ZLOUT asserts to logical 1 when the load lies within this hatched region.
Содержание SEL-311B
Страница 6: ......
Страница 8: ......
Страница 10: ......
Страница 24: ......
Страница 26: ......
Страница 122: ......
Страница 124: ......
Страница 138: ......
Страница 168: ......
Страница 172: ......
Страница 254: ......
Страница 282: ......
Страница 306: ......
Страница 348: ......
Страница 364: ......
Страница 366: ......
Страница 448: ......
Страница 460: ......
Страница 466: ......
Страница 476: ......
Страница 482: ......
Страница 494: ......
Страница 500: ......
Страница 522: ......
Страница 526: ......
Страница 528: ......
Страница 534: ......
Страница 536: ......
Страница 550: ......
Страница 570: ......
Страница 586: ......
Страница 600: ......