14-38
Application Settings for SEL-221 Series Relays
Date Code 20011205
SEL-311B Instruction Manual
SEL-311B
Relay
Setting
Calculated from SEL-221C
Settings
SEL-311B Instruction
Manual Section
SEL-221C Instruction
Manual Section
79OI1
= 79OI1
Section 6—Close and
Reclose Logic
Section 2—Reclosing
Relay
79OI2 =
79OI2
79OI3 =
79OI3
79RSD
None (SEL-221C setting 79RS
serves a slightly different
purpose.)
Section 6—Reclosing
Relay Timer Settings
79RSLD None
52AEND
= 52BT (Pickup)
Section 5—Switch-
Onto-Fault (SOTF) Trip
Logic
Section 5—52BT
Setting (52BT) and
Switch-Onto-Fault
Protection
SOTFD
= 52BT (Dropout)
TDURD
= TDUR
Section 4—Unlatch
Trip
Section 5—Trip
Duration Timer
(TDUR)
SV1PU
= 50MFD
Section 5—Medium Set
Overcurrent Setting
(50M)
SV9DO
= VCT
Section 2—Reclosing
Relay
* Curve U1 in the SEL-311B is slightly different from curve 1 in the SEL-221C. Time dial
adjustments may be necessary.
Note:
SEL-311B phase-to-phase fault detector settings 50PP1, 50PP2, and 50PP3 are set to
0.1 * I
NOM
and are hidden. This corresponds to SEL-221C setting 50L.
Содержание SEL-311B
Страница 6: ......
Страница 8: ......
Страница 10: ......
Страница 24: ......
Страница 26: ......
Страница 122: ......
Страница 124: ......
Страница 138: ......
Страница 168: ......
Страница 172: ......
Страница 254: ......
Страница 282: ......
Страница 306: ......
Страница 348: ......
Страница 364: ......
Страница 366: ......
Страница 448: ......
Страница 460: ......
Страница 466: ......
Страница 476: ......
Страница 482: ......
Страница 494: ......
Страница 500: ......
Страница 522: ......
Страница 526: ......
Страница 528: ......
Страница 534: ......
Страница 536: ......
Страница 550: ......
Страница 570: ......
Страница 586: ......
Страница 600: ......