85/90
User manual SCAIME:
NU-Soft-eNod4F-E-0716_235704-C.doc
Chapter
Name
Modbus
address
CANopen®
Index/sub-index
Profibus
cyclic
IN/OUT
Acyclic
DPV1
slot/index
Type Access
Dosing
Totalizer value (Great
WU)
0x008D 0x5006 / 0x01 (M)
R : 0x04F0
+ See
modules list
/
Ulong RO
Dosing
Complementary totalizer
value
0x008F
0x5006 / 0x02 (M)
R : 0x02F2
+ See
modules list
/
Uint
RO
Commands
Command register
0x0090
0x2003 / 0x00 (M) Module 6
/
Uint
RW
Commands
Response register
0x0091
0x2004 / 0x00 (M) Module 6
/
Uint
RO
Calibration
Zero offset
0x0092
0x2500 / 0x00 (M)
R : 0x0472
W: 0x0473
0x03 / 0x03 Long
RW
Inputs/outputs
Logical input level
0x0094
LSB
0x5100 / 0x00 (M)
Module 2
/
Byte
RO
Inputs/outputs
Logical ouput level
0x0094
MSB
0x5200 / 0x00 (M)
Byte
Dosing
Dosing weight deviation
0x0095
0x5007 / 0x05 (M)
R : 0x04FA
+ See
modules list
/
float
RO
Measures
Preset Tare
0x0097
0x5004 / 0x02 (M)
R : 0x04C4
W : 0x04C5
0x03 / 0x08 Ulong RW
Reserved (2 bytes)
0x0099
Dosing
Dosing status
0x009A 0x5007 / 0x01 (M)
R : 0x02FC
+ See
modules list
/
Uint
RO
Dosing
Dosing errors report
0x009B
0x5007 / 0x02 (M)
R : 0x02FE
+ See
modules list
/
Uint
RO
Dosing
Dosing errors counter
0x009C
0x5007 / 0x03 (M)
R : 0x023E
+ See
modules list
/
Uint
RO
Dosing
Last dosing error
0x009D 0x5007 / 0x05 (M)
R : 0x024A
+ See
modules list
/
Uint
RO
Dosing
Dosing quality factor
0x009E
0x5005 / 0x04 (M)
R : 0x04EE
+ See
modules list
/
float
RO
Dosing
Totalization flow rate
0x00A0 0x5006 / 0x03 (M)
R : 0x04F8
+ See
modules list
/
float
RO
Dosing
Grand total (Great WU)
0x00A2 0x5006 / 0x04 (M)
R : 0x04F4
+ See
modules list
/
Ulong RO