Example applications
4-2
4
4.4
Configuration
The compact room controllers can be parameterised very efficiently. Where a set
of room controllers with consecutive S-Bus addresses are to be configured with the
same basic parameters using the Autoconfiguration function, a single Config FBox
can distribute the parameters to all the room controllers automatically. To do this,
the start and end addresses are entered into the Config FBox in the "from station
address" and "to station address" parameters and "Autoconfiguration" is set to
"active".
Configuration can also be carried out manually. To do this, the "Autoconfiguration"
parameter is set to "inactive". The "Write" button then causes the whole parameter
set to be copied over to all station addresses from "from station adddress" to "to
station address".
If a station address within a selected range was not configured successfully, the
Config FBox interrupts Autoconfiguration at this point and displays "Error" in the
right of the window next to the Write button, with the relevant station number below.
When writing, whether automatically or manually, all parameters are stored directly
in the room controller's EEPROM. The previous settings are then lost.
To read the parameters, it is sufficient to enter the S-Bus address in the "from station
address" parameter. The "Read out" button causes the data to be passed from the
room controller to the FBox.