Saia-Burgess Controls AG
Manual for PCD7.L79xN room controllers
│
Document 27 / 602
E
N02 │ 2013-11-27
Registers, actual values
Register usage
5-6
5
Registers
R/W
Description
Actual values
36
R/W
Operating mode - default
0 The controller works permanently in "Comfort" mode. The room control unit no
longer has any effect.
1 The controller works in "Reduced" mode. If the controller detects a presence,
"Comfort" mode is activated for a configurable period (see register 0).
2 The controller works in "Standby" mode. According to whether a presence is
detected, the controller switches between "Comfort" and "Standby" mode.
5 The controller works permanently in "Reduced" mode. Presence detection has
no effect.
38
R/W
Change-over status. (See Configuration register 10)
0=Heating, 1=Cooling
39
R/W
Dew point status. (See Configuration register 10)
0=dry, 1=condensation
59
R
Current operating mode
0="Comfort" 1="Reduced" 2="Standby"
Outputs
45
R/W
Manual control of Y3 (0
… 10 V) where the output is not used by the application.
(See Configuration register 103)
Or control of the valve Y3 in the application selection “RIO”
(see HW configuration registers 9)
Unit: [%], range: 0
…
100 (0
…
100% = 0
…
10 V)
46
R/W
Manual control of Y4 (0
… 10 V) where the output is not used by the application.
(See Configuration register 103)
Or control of the valve Y4 in the application selection “RIO”
(see HW configuration registers 9)
Unit: [%], range: 0
…
100 (0
…
100% = 0
…
10 V)
47
L/S
Manual control of
Y1 (PWM)
where the output is not used by the
application. (See Configuration register 103)
.
Or control of the valve Y1 in the application selection “RIO”
(see HW configuration registers 9)
Unit: [%], range: 0
…
100
48
L/S
Manual control of
Y2 (PWM)
where the output is not used by the
application. (See Configuration register 103)
.
Or control of the valve Y2 in the application selection “RIO”
(see HW configuration registers 9)
Unit: [%], range: 0
…
100