Saia-Burgess Controls AG
Manual for PCD7.L79xN room controllers
│
Document 27 / 602
E
N02 │ 2013-11-27
Functions, settings
Function
3-6
3
3.2.1 Functions, settings, room control unit
Set-point step in K (register 104)
The room control unit can increase or decrease the room set-point for the controller in
up to 6 steps. The absolute change in the set-point is defined by the number of steps
set on the room control unit and this parameter for the difference per step.
Range of settings:
FBox
0 ... 1 K
Registers 0 ... 10 K/10
3.2.2 Functions, settings, operation
Choice of application (register 9)
The regulation/control functions are dependent on the program selected. This register
x. is used to define the program. The associated outputs Y1…Y4 are specified in the
"Hardware" section. All outputs not used by the function can be freely used for RIO
(remote input-output).
Application
Description
Terminals
Y1
Triac PWM output 0…100 %
Y1
Y2
Triac PWM output 0…100 %
Y2
Y3
Analogue 0…10 V output 0…100 %
Y3
Y4
Analogue 0…10 V output 0…100 %
Y4