Functions, settings
Function
3-16
3
Heating reset time in s ... (register 106)
Run-down time for the heating PI controller in seconds. The value 0 blocks the inte-
ger portion.
Range of settings: (default 0 seconds)
FBox
0
…
1000 s
Registers
0
…
1000 s
Limitation heating % (register 141)
After a restart, the maximum output value for heating (HeatY) is limited.
Range of settings: (default 100 %)
FBox
0…100 %
Registers 0…100 %
Coasting comfort mode ×10min (register 1)
Where the controller is working in unused mode, a presence alert causes it to
switch to Comfort mode for a configurable period of time. At the end of this time, the
controller automatically returns to unused mode.
Range of settings: (default 6 → 60
mins)
FBox
0
…
240 × 10 mins
Registers
0
…
240 × 10 mins