Saia-Burgess Controls AG
Manual for PCD7.L79xN room controllers
│
Document 27 / 602
E
N02 │ 2013-11-27
Registers, configuration
Register usage
5-4
5
Registers
Description
103
0
The outputs pass a PWM signal to the Triac outputs.
1
The outputs pass a constant signal to the 0…10 V outputs.
2
Heat on PWM Y1 / Cool on 0…10 V Y4.
3
Heat on 0…10 V Y3 / Cool on PWM Y2.
4
Use of Triac outputs as a 3-point signal for a 3-point valve. The valve run time is
given by the "PWM cycle time" parameter in register 11.
5
Bullet valve on Y3 (heating & cooling).
105
Window contact polarity.
0
When the window is closed, the window contact is also closed.
1
When the window is closed, the window contact is open.
Control parameters
0
Run-down time in Comfort mode in 10-minute steps.
Range: 0
…
24 = 0
…
240 minutes, default: 0 = 0 minutes
2
Neutral zone in "Comfort" mode, unit:[K/10]
Range: 0
…
200 (=0
…
1.0 K/step), Default: 20
3
Neutral zone in "Standby" mode, unit:[K/10]
Range: 10
…
200 (=1
…
1.0 K/step), Default: 40
4
Neutral zone in "Reduced" mode, unit:[K/10]
Range: 10
…
200 (=1
…
1.0 K/step), Default: 60
5
Proportional band for cooling, unit:[K/10]
Range: 5
…
100 (=0,5..10,0 K), default: 50
7
Run-down time for cooling, unit: [seconds].
A value of 0 disables the integer portion, pure P control.
Range: 0
…
1000 seconds, default: 0
6
Proportional band for heating, unit:[K/10]
Range: 5
…
100 (=0,5..10,0 K), default: 50
37
Base set-point for initialising the controller after a restart, unit [°C/10]
Range: 100
…
350 (= 10.0
…
35.0°C), default: 22
106
Run-down time for heating, unit: [seconds].
A value of 0 disables the integer portion, pure P control.
Range: 0
…
1000 seconds, default: 0
140
Valve limit for cooling (CoolY)
Range: 0…100%, default: 100
141
Valve limit for heating (HeatY)
Range: 0…100%, default: 100