93
Setting
value
Function
Description
14
Torque limited
In the speed control mode of the frequency converter, when the
output torque reaches the torque limit value, the frequency
converter is in the stall protection state and outputs an ON signal at
the same time.
15
Ready for run
When the power supply of the main circuit and the control circuit of
the inverter has stabilized, and the inverter has not detected any
fault information, and the inverter is in a operable state, it outputs an
ON signal.
16
AVI1>AVI2/ACI
When the value of analog input AVI1 is greater than the input value
of AVI2/ACI, an ON signal is output.
17
Upper limit frequency reached
When the running frequency reaches the upper limit frequency, the
ON signal is output.
18
Lower limit frequency reached
(operation valid)
When the running frequency reaches the lower limit frequency, the
ON signal is output. The output is OFF in the stop state.
19
Undervoltage state output
When the inverter is undervoltage state, it outputs ON signal.
20
Communication setting
Please refer to the communication protocol.
21
Reserved
Reserved
22
Reserved
Reserved
23
Zero speed running 2 (also
output when stopped)
When the output frequency of the inverter is 0, the ON signal is
output. This signal is also ON in the stop state.
24
Cumulative power-on time
arrival
When the cumulative power-on time (08-13) of the inverter exceeds
the set time of 09-16, it outputs an ON signal.
25
Frequency level detection
FDT2 output
Please refer to the parameters 09-28,09-29
26
Frequency 1 reaches the
output
Please refer to the parameters 09-30,09-31
27
Frequency 2 reaches the
output
Please refer to the parameters 09-32,09-33
28
Current 1 reaches the output
Please refer to the parameters 09-38,09-39
29
Current 2 reaches the output
Please refer to the parameters 09-40,09-41
30
Timing reached
When the timing function selection (09-42) is valid, the inverter will
output an ON signal after the current running time of the inverter
reaches the set time.
31
AVI1 input exceeds limit
When the value of analog input AVI1 is greater than 09-46 (AVI1
input protection upper limit) or less than 09-45 (AVI1 input protection
lower limit), ON signal is output.
32
Lost load
When the inverter is in the load drop state, it outputs ON signal.
33
Reverse running
When the inverter is running in reverse, output ON signal
34
Zero current state
Please refer to the parameters 09-34,09-35
35
Module temperature reached
Inverter module radiator temperature (08-08) reaches the set
module temperature reached value(09-47), output ON signal
36
Software current limit
exceeded
Please refer to the parameters 09-36,09-37
Содержание S3100A Series
Страница 1: ...S3100Aseries inverter General Open loop Vector Control IM User manual User Manual ...
Страница 23: ...19 Size 3 Unit mm S3100A 2T5 5G 2T7 5G S3100A 4T7 5G 11P 4T18 5G 22P Size 4 Unit mm S3100A 4T22G 30P 4T37G 45P ...
Страница 24: ...20 Size 5 Unit mm S3100A 4T45G 55P 4T110G Size 6 Unit mm S3100A 4T110G 132P 4T160G 185P ...
Страница 25: ...21 Size 7 Unit mm S3100A 4T185G 200P 4T220G Size 8 Unit mm S3100A 4T220G 250P 4T315G ...
Страница 26: ...22 Size 9 Unit mm S3100A 4T315G 355P 4T400G 450P Size 10 Unit mm S3100A 4T450G 500P 4T500G ...