When you need to run, you must first close the MIn terminal, the MIx pulse rising edge generates the motor
running signal, and the MIy state generates the motor direction signal.
When it is necessary to stop, it must be achieved by disconnecting the terminal signal of the MIn terminal. Among
them, MIx, MIy, and MIn are the multi-function input terminals of MI1 to MI5, MIx is pulse effective, and MIy, MIn
are level effective.
SB1
SB2
S3100A
K
MIx
MIy
DCM
MIn
K
RUN
command
Forward
Reverse
1
0
SB2
:
RUN button
SB1
:
Stop button
Forward RUN (FWD)
Reverse RUN (REV)
Digital common
Three wire control
Figure 5-9 Three-wire control mode 2
04-10
Terminal UP/DOWN change rate
Factory setting
1.00Hz/s
Setting range 0.01Hz/s
~
65.535Hz/s
Used to set the terminal UP/DOWN to adjust the set frequency, the speed of frequency change, that is the
amount of frequency change per second.
When 00-25 (frequency decimal point) is 2, the value range is 0.001Hz/s
~
65.535Hz/s. When 00-25 (frequency
decimal point) is 1, the value range is 0.01Hz/s
~
655.35Hz/s.
04-11
AVI curve 1 lower limit
Factory setting
0.10V
Setting range 0.00V
~
04-13
04-12
Corresponding setting of AVI curve 1 lower limit
Factory setting
0.0%
Setting range -100.0%
~
+100.0%
04-13
AVI curve 1 upper limit
Factory setting
10.00V
Setting range 04-11
~
+10.00V
04-14
Corresponding setting of AVI curve 1 upper limit
Factory setting
100.0%
Setting range -100.0%
~
+100.0%
04-15
AVI1 filter time
Factory setting
0.10s
Setting range 0.00s
~
10.00s
The relationship between the above parameter analog input voltage and the setting value it represents.
When the analog input voltage exceeds the set range of the maximum input or minimum input, it will be calculated
as the maximum input or minimum input.
When the analog input is current input, 0mA
~
20mA current corresponds to 0V
~
5V Voltage.
In different applications, the meaning of the nominal value corresponding to 100.0% of the analog setting is
different. For details, please refer to the description of each application.
Содержание S3100A Series
Страница 1: ...S3100Aseries inverter General Open loop Vector Control IM User manual User Manual ...
Страница 23: ...19 Size 3 Unit mm S3100A 2T5 5G 2T7 5G S3100A 4T7 5G 11P 4T18 5G 22P Size 4 Unit mm S3100A 4T22G 30P 4T37G 45P ...
Страница 24: ...20 Size 5 Unit mm S3100A 4T45G 55P 4T110G Size 6 Unit mm S3100A 4T110G 132P 4T160G 185P ...
Страница 25: ...21 Size 7 Unit mm S3100A 4T185G 200P 4T220G Size 8 Unit mm S3100A 4T220G 250P 4T315G ...
Страница 26: ...22 Size 9 Unit mm S3100A 4T315G 355P 4T400G 450P Size 10 Unit mm S3100A 4T450G 500P 4T500G ...