105
09-04
Deceleration time 2
Factory setting
Type setting
09-05
Acceleration time 3
Factory setting
Type setting
09-06
Deceleration time 3
Factory setting
Type setting
09-07
Acceleration time 4
Factory setting
Type setting
09-08
Deceleration time 4
Factory setting
Type setting
Setting range 0. 0s
~
6500.0s
S3100A provides 4 groups of acceleration and deceleration time, respectively 00-07/00-08 and the above 3
groups of acceleration and deceleration time.
The definitions of the 4 groups of acceleration and deceleration times are exactly the same, please refer to the
relevant descriptions of 00-07 and 00-08. Through different combinations of multi-function digital input terminals
MI, you can switch to select 4 groups of acceleration and deceleration time. For specific usage, please refer to the
relevant descriptions in parameters 04-00
~
04-05.
09-09
Jump frequency 1
Factory setting
0.00Hz
Setting range 0.00Hz
~
Max frequency
09-10
Jump frequency 2
Factory setting
0.00Hz
Setting range 0.00Hz
~
Max frequency
09-11
Jump frequency amplitude
Factory setting
0.00Hz
Setting range 0.00Hz
~
Max frequency
When the set frequency is within the range of the jump frequency, the actual operating frequency will run at the
jump frequency closer to the set frequency. By setting the jump frequency, the inverter can avoid the mechanical
resonance point of the load.
The S3100A can set two jump frequency points. If both jump frequencies are set to 0, the jump frequency function
is cancelled. Please refer to Figure 5-15 for the principle of jump frequency and jump frequency amplitude.
Output frequency
Hz
Time
Jump frequency 2
Jump frequency amplitude
Jump frequency 1
Jump frequency amplitude
Jump frequency
amplitude
Jump frequency
amplitude
Figure 5-15 Schematic diagram of jumping frequency
09-12
Forward and reverse dead time
Factory setting
0.0s
Setting range 0.00s
~
3000.0s
Содержание S3100A Series
Страница 1: ...S3100Aseries inverter General Open loop Vector Control IM User manual User Manual ...
Страница 23: ...19 Size 3 Unit mm S3100A 2T5 5G 2T7 5G S3100A 4T7 5G 11P 4T18 5G 22P Size 4 Unit mm S3100A 4T22G 30P 4T37G 45P ...
Страница 24: ...20 Size 5 Unit mm S3100A 4T45G 55P 4T110G Size 6 Unit mm S3100A 4T110G 132P 4T160G 185P ...
Страница 25: ...21 Size 7 Unit mm S3100A 4T185G 200P 4T220G Size 8 Unit mm S3100A 4T220G 250P 4T315G ...
Страница 26: ...22 Size 9 Unit mm S3100A 4T315G 355P 4T400G 450P Size 10 Unit mm S3100A 4T450G 500P 4T500G ...