This parameter is used to select the feedback signal channel of the process PID.
The feedback value of the process PID is also a relative value, and the setting range is 0.0%~100.0%.
10-03
PID action direction
Factory setting
0
Setting range
0
Positive action
1
Reaction
Positive effect: When the PID feedback signal is less than the given amount, the output frequency of the inverter
rises. Such as tension control in winding.
Reverse effect: When the PID feedback signal is less than the given amount, the output frequency of the inverter
decreases. Such as unwinding tension control occasions.
This function is affected by the multi-function terminal "PID reverse direction" (function 35), which needs attention
during use.
10-04
PID Given feedback range
Factory setting
1000
Setting range 0
~
65535
PID given feedback range is a dimensionless unit, used for PID given display 99-15 and PID feedback display
99-16.
The relative value of PID given feedback is 100.0%, corresponding to the given feedback range 10-04.
For example, if 10-04 is set to 2000, when PID setting is 100.0%, PID setting displays 99-15 to 2000.
10-05
Proportional gain Kp1
Factory setting
20.0
Setting range 0.0
~
999.9
10-06
Integration time Ti1
Factory setting
2.00s
Setting range 0.01s
~
10.00s
10-07
Differential time Td1
Factory setting
0.000s
Setting range 0.000s
~
10.000s
Proportional gain Kp1:
Determines the adjustment intensity of the entire PID regulator. The greater the Kp1, the greater the adjustment
intensity.The parameter 100.0 indicates that when the deviation between the PID feedback amount and the given
amount is 100.0%, the adjustment range of the PID regulator for the output frequency command is the maximum
frequency.
Integration time Ti1:
Determine the intensity of PID regulator integral adjustment.The shorter the integration time, the greater the
adjustment intensity. The integration time refers to the amount of PID feedback
When the deviation from the given amount is 100.0%, the integral regulator continuously adjusts after this time,
and the adjustment amount reaches the maximum frequency.
Содержание S3100A Series
Страница 1: ...S3100Aseries inverter General Open loop Vector Control IM User manual User Manual ...
Страница 23: ...19 Size 3 Unit mm S3100A 2T5 5G 2T7 5G S3100A 4T7 5G 11P 4T18 5G 22P Size 4 Unit mm S3100A 4T22G 30P 4T37G 45P ...
Страница 24: ...20 Size 5 Unit mm S3100A 4T45G 55P 4T110G Size 6 Unit mm S3100A 4T110G 132P 4T160G 185P ...
Страница 25: ...21 Size 7 Unit mm S3100A 4T185G 200P 4T220G Size 8 Unit mm S3100A 4T220G 250P 4T315G ...
Страница 26: ...22 Size 9 Unit mm S3100A 4T315G 355P 4T400G 450P Size 10 Unit mm S3100A 4T450G 500P 4T500G ...