74
11: V/f half separation mode. In this mode, V and F are proportional, but the proportional relationship can be set
by voltage source 03-13, and the relationship between V and F is also related to the rated voltage and rated
frequency of motor group 01.
Assuming that the voltage source input is X (X is a value of 0~100%), the relationship between the output voltage
V of the inverter and the frequency F is:V/f=2 * X * (motor rated voltage)/(motor rated frequency)
03-01
Torque boost
Factory setting
Type setting
Setting range
0.0%:( auto-torque boost)
0.1%
~
30.0%
03-02
Cut-off frequency of torque boost
Factory setting
50.00Hz
Setting range 0.00Hz
~
max frequency
Torque boosting can improve the low-frequency torque characteristics of V/f and do boost compensation for the
output voltage. However, if the torque boost setting is too large, the motor is easily overheated and the inverter is
easily overcurrent.
When the torque boost is set to 0.0, the inverter is in automatic torque boost, and the inverter automatically
calculates the torque boost value according to the motor stator resistance and other parameters.
Torque boost torque cut-off frequency: Below this frequency, the torque boost is valid, and beyond this set
frequency, the torque boost is invalid, as shown in Figure 5-3.
Output
voltage
Output
frequency
fb
Vb
V1
f1
V1: Manual torque boost voltage Vb: Maximum output voltage
f1: Cut-off frequency of manual torque boost fb: Rated running frequency
Figure 5-3 Schematic diagram of manual torque boost
03-03
Multi-point V/f frequency point 1
Factory setting
0.00Hz
Setting range 0.00Hz
~
03-05
03-04
Multi-point V/f voltage point 1
Factory setting
0.0%
Setting range 0.0%
~
100.0%
03-05
Multi-point V/f frequency point 2
Factory setting
0.00Hz
Setting range 03-03
~
03-07
03-06
Multi-point V/f voltage point 2
Factory setting
0.0%
Setting range 0.0%
~
100.0%
Содержание S3100A Series
Страница 1: ...S3100Aseries inverter General Open loop Vector Control IM User manual User Manual ...
Страница 23: ...19 Size 3 Unit mm S3100A 2T5 5G 2T7 5G S3100A 4T7 5G 11P 4T18 5G 22P Size 4 Unit mm S3100A 4T22G 30P 4T37G 45P ...
Страница 24: ...20 Size 5 Unit mm S3100A 4T45G 55P 4T110G Size 6 Unit mm S3100A 4T110G 132P 4T160G 185P ...
Страница 25: ...21 Size 7 Unit mm S3100A 4T185G 200P 4T220G Size 8 Unit mm S3100A 4T220G 250P 4T315G ...
Страница 26: ...22 Size 9 Unit mm S3100A 4T315G 355P 4T400G 450P Size 10 Unit mm S3100A 4T450G 500P 4T500G ...