64
Used to change the direction of the motor, its role is equivalent to changing the direction of motor rotation by
adjusting any two motor lines.
Note: After the parameters are initialized, the motor running direction will return to its original state. For occasions
where it is strictly forbidden to change the direction of the motor after system debugging, please use it with
caution.
00-10
Carrier frequency
Factory setting
Type setting
Setting range 0.5kHz
~
12.0kHz
This function adjusts the carrier frequency of the inverter. By adjusting the carrier frequency can reduce the motor
noise, avoid the resonance point of the mechanical system, reduce the line leakage current to the ground and
reduce the interference generated by the inverter.
The advantages of high carrier frequency: the current waveform is ideal, the current harmonics are less, and the
motor noise is small;
Disadvantages of high carrier frequency: increased switching loss, increased temperature rise of the inverter, and
affected the output capacity of the inverter. Under high carrier frequency, the inverter needs to be derated; at the
same time, the leakage current of the inverter increases, which Increased electromagnetic interference.
The effect of carrier frequency on the following performance:
Carrier frequency
Low
→
High
Motor noise
Large
→
Small
Output current waveform
Bad
→
Good
Motor temperature rise
High
→
Low
Inverter temperature rise
Low
→
High
Leakage current
Small
→
Large
External radiation interference
Small
→
Large
The factory setting of carrier frequency is different according to different power models. The user can modify it as
needed, but it should be noted that if the carrier frequency is set higher than the factory value, it will cause the
temperature rise of the inverter radiator to increase. At this time, the user needs to derate the inverter, otherwise
the inverter will be in danger of overheating.
00-11
Parameter initialization
Factory setting
0
Setting range
0
No operation
1
Restore factory parameters, excluding motor parameters
2
Clear record information
1. Restore the factory settings, most of the inverter parameters are restored to the factory values, but the motor
parameters, frequency command decimal point (00-25), fault record information, cumulative running time
(08-11), cumulative power-on time (08-13), the cumulative power consumption (08-14) does not recover.
2. Clear record information
Clear the inverter fault record information, cumulative running time (08-11), cumulative power-on time (08-13),
cumulative power consumption (08-14).
Note: The parameter value automatically returns to 0 after the operation is completed.
Содержание S3100A Series
Страница 1: ...S3100Aseries inverter General Open loop Vector Control IM User manual User Manual ...
Страница 23: ...19 Size 3 Unit mm S3100A 2T5 5G 2T7 5G S3100A 4T7 5G 11P 4T18 5G 22P Size 4 Unit mm S3100A 4T22G 30P 4T37G 45P ...
Страница 24: ...20 Size 5 Unit mm S3100A 4T45G 55P 4T110G Size 6 Unit mm S3100A 4T110G 132P 4T160G 185P ...
Страница 25: ...21 Size 7 Unit mm S3100A 4T185G 200P 4T220G Size 8 Unit mm S3100A 4T220G 250P 4T315G ...
Страница 26: ...22 Size 9 Unit mm S3100A 4T315G 355P 4T400G 450P Size 10 Unit mm S3100A 4T450G 500P 4T500G ...