Frequency arrival
detection signal
(
MO1,RELAY,DFM(M)
Output frequency Hz
FDT Level
FDT hysteresis
ON
Time
Time
=09-19x09-20
Figure 5-17 Schematic diagram of FDT level
09-21
Frequency reach detection width
Factory setting
0.0%
Setting range 0.00
~
100%(Max frequency )
When the running frequency of the inverter is within a certain range of the target frequency, the multi-function
output terminal (function 4) of the inverter outputs an ON signal.
This parameter is used to set the detection range of frequency arrival. This parameter is a percentage relative to
the maximum frequency. Figure 5-18 is a schematic diagram of frequency arrival.
Frequency arrival
detection signal
Output frequency Hz
Set frequency
Detection
amplitude
ON
Time
ON
Figure 5-18 Schematic diagram of the frequency arrival detection amplitude