65
00-12
Carrier frequency adjusts with temperature
Factory setting
1
Setting range
0
No automatic carrier reduction
1
Automatic carrier reduction
2
Low noise
The carrier frequency is adjusted with the temperature. When the inverter detects that the radiator temperature is
high, the carrier frequency is automatically reduced to prevent the inverter temperature from rising too high and
reduce the overheating alarm. When the temperature of the radiator drops, the carrier frequency automatically
returns to the set value.
00-14
Auxiliary frequency source Y selection
(Refer to 00-02)
Factory setting
0
Setting range
0
Digital setting (keyboard given frequency 00-06, UP /DOWN can be
modified)
1
AVI1
2
AVI2/ACI
3
Reserved
4
Multi-speed command
5
PID control
6
Communication setting
7
Simple PLC
8
Panel potentiometer
9
Pulse setting (MI5)
When the auxiliary frequency source is used independently as the frequency reference channel (that is, the
frequency source selection is switched to Y), the method of use is the same as the main frequency source X. You
can refer to the 00-02 instructions.
When the auxiliary frequency source is given as a superposition (that is, the frequency source is selected as X+Y,
X to X+Y switching or Y to X+Y switching), please note:
(1) When the auxiliary frequency source selects the digital setting, the given frequency (00-06) of the keyboard
does not work, a
nd the frequency can be adjusted by the ▲ and ▼ keys of the keyboard (or UP and DOWN of the
multi-function input terminal). The frequency is adjusted on the basis of the main frequency.
(2) When the auxiliary frequency source selects analog (AVI1, AVI2/ACI) or pulse input as the timing, the input
setting 100% corresponds to the frequency range, which can be set by 00-15 and 00-16.
Note: The setting values of 00-02 and 00-14 cannot be the same, that is, the auxiliary frequency source Y and the
main frequency source X cannot select the same channel, otherwise the operation may be messy.
00-15
Selection of auxiliary frequency source Y range during stacking
Factory setting
0
Setting range
0
Relative to the maximum frequency
1
Relative to the main frequency source X
Содержание S3100A Series
Страница 1: ...S3100Aseries inverter General Open loop Vector Control IM User manual User Manual ...
Страница 23: ...19 Size 3 Unit mm S3100A 2T5 5G 2T7 5G S3100A 4T7 5G 11P 4T18 5G 22P Size 4 Unit mm S3100A 4T22G 30P 4T37G 45P ...
Страница 24: ...20 Size 5 Unit mm S3100A 4T45G 55P 4T110G Size 6 Unit mm S3100A 4T110G 132P 4T160G 185P ...
Страница 25: ...21 Size 7 Unit mm S3100A 4T185G 200P 4T220G Size 8 Unit mm S3100A 4T220G 250P 4T315G ...
Страница 26: ...22 Size 9 Unit mm S3100A 4T315G 355P 4T400G 450P Size 10 Unit mm S3100A 4T450G 500P 4T500G ...