104
08-12
Load speed display the number of decimal places
Factory setting
20
Setting range
Units: Number of decimal places for load speed
Tens place:Number of decimal places for feedback speed
0
0 decimal place
1
1 decimal place
2
2 decimal places
3
3 decimal places
Used to set the number of decimal places for load speed display.The following example illustrates the calculation
method of load speed:
If the load speed display coefficient 08-06 is 2.000, the load speed decimal point number 08-12 is 2 (2 decimal
points), when the inverter running frequency is 40.00Hz, the load speed is: 40.00*2.000 = 80.00 (2 decimal points
display)
If the inverter is in a stopped state, the load speed is displayed as the speed corresponding to the setting
frequency,that is, "set load speed". Taking the set frequency of 50.00Hz as an example, the load speed in the stop
state is: 50.00*2.000 = 100.00 (2 decimal places display)
08-13
Cumulative power-on time
Factory setting
-
Shows the cumulative power-on time of the inverter since the factory.
When this time reaches the set power-on time (09-17), the inverter's multi-function digital output function (24)
outputs an ON signal.
08-14
Cumulative power consumption
Factory setting
-
Setting range 0
~
65535 degree
Displays the cumulative power consumption of the inverter so far
09 Accessibility Parameters
09-00
Jog
running frequency
Factory setting
5.00Hz
Setting range 0.00Hz
~
Max frequency
09-01
Jog acceleration time
Factory setting
20.0s
Setting range 0.0s
~
6500.0s
09-02
Jog deceleration time
Factory setting
20.0s
Setting range 0.0s
~
6500.0s
Define the given frequency and acceleration/deceleration time of the inverter when jogging.
During jog operation, the start mode is fixed to the direct start mode (07-00=0), and the stop mode is fixed to the
deceleration stop (07-05=0).
09-03
Acceleration time 2
Factory setting
Type setting
Содержание S3100A Series
Страница 1: ...S3100Aseries inverter General Open loop Vector Control IM User manual User Manual ...
Страница 23: ...19 Size 3 Unit mm S3100A 2T5 5G 2T7 5G S3100A 4T7 5G 11P 4T18 5G 22P Size 4 Unit mm S3100A 4T22G 30P 4T37G 45P ...
Страница 24: ...20 Size 5 Unit mm S3100A 4T45G 55P 4T110G Size 6 Unit mm S3100A 4T110G 132P 4T160G 185P ...
Страница 25: ...21 Size 7 Unit mm S3100A 4T185G 200P 4T220G Size 8 Unit mm S3100A 4T220G 250P 4T315G ...
Страница 26: ...22 Size 9 Unit mm S3100A 4T315G 355P 4T400G 450P Size 10 Unit mm S3100A 4T450G 500P 4T500G ...