Design
D - 21
3) Flow in area determination
From the flow in area required, calculated in 1), and the effective flow in area calculated in 2)-C), it is necessary to
fulfill the following two conditions.
1) The overall effective flow in area
‚r
et must be greater than the required flow in area Sr.
2) For a layout with 3 or more rows, the smallest value of the area of two adjoining walls Se
12
.
Se
23
.
Se
34
.
Se
41
shall be
greater than 25% of Sr. min (Se
1
.
Se
23
.
Se
34
.
Se
41
) 0.25×Sr
*Where these conditions are not fulfilled, apply the following measures and re-investigate.
●
Increase the upstand height
●
Install a blow out duct return to item
5
-
●
Change the foundations to a cat walk
●
Increase the opening rate in the walls
●
Lower the height of the walls return to item
5
- -2)
●
Increase the distance from wall to unit
Correction of cooling capability
As a result of this criterion, the temperature of the intake air in this combined installation is expected to rise by 3
o
C
during cooling.
Obtain the reduction in cooling capability for each unit from the characteristics for that model type.
(2)Verandah installation criterion
If an outdoor unit is installed on a verandah, where it is surrounded by walls on 5 sides, it is necessary to design the
layout taking short circuits and maintenance space into mind. For installation on each floor of a building is evaluated in
the same way in accordance with the criteria.
1
Design points
1) Do not allow the exhaust air from an outdoor unit to create a short circuit, causing the capability of the system to
reduce remarkably.
2) Do not install a gallery on the exhaust outlet.
(Installing a gallery reduces the wind quantity by over 10%)
3) Create an environment in which exhaust air from the outdoor unit will not cause trouble.
4) Satisfy the local regulations regarding operating noise from outdoor units.
5) The distance to the adjacent building should be at least 10m.
6) The design external air conditions are 35
o
CDB or less.
7) Make sure to provide maintenance space.
2
Necessary flow in area
1) For an installation as shown in Figure 1, the shaded area shown in Figure 1 is the flow in area.
2) The necessary flow in area for one outdoor unit is 5m
2
for 8, 10 HP, 10m
2
for 13~20HP, so the shaded area is the
necessary flow in area.
5. Criteria for positioning the outdoor unit
Содержание SGP-E120J2GU2
Страница 19: ...Outdoor Unit B 14 290 Type Performance characteristics of SGP E90J2GU2 5 Performance characteristics ...
Страница 20: ...Outdoor Unit B 15 3120 Type Performance characteristics of SGP E120J2GU2 5 Performance characteristics ...
Страница 21: ...Outdoor Unit B 16 4150 Type Performance characteristics of SGP E150J2GU2 5 Performance characteristics ...
Страница 22: ...Outdoor Unit B 17 5190 Type Performance characteristics of SGP E190J2GU2 5 Performance characteristics ...
Страница 49: ...Design D 5 2 Operating temperature ranges for heating and cooling Cooling Heating ...
Страница 87: ...Design D 43 8 Salt resistant specification ...
Страница 109: ...Construction E 22 4 Outdoor unit installation and construction ...
Страница 110: ...Construction E 23 4 Outdoor unit installation and construction ...
Страница 111: ...Construction E 24 4 Outdoor unit installation and construction ...
Страница 112: ...Construction E 25 4 Outdoor unit installation and construction ...
Страница 113: ...Construction E 26 4 Outdoor unit installation and construction ...
Страница 114: ...Construction E 27 4 Outdoor unit installation and construction ...
Страница 115: ...Construction E 28 4 Outdoor unit installation and construction ...
Страница 116: ...Construction E 29 4 Outdoor unit installation and construction ...
Страница 117: ...Construction E 30 4 Outdoor unit installation and construction ...
Страница 118: ...Construction E 31 4 Outdoor unit installation and construction ...
Страница 119: ...Construction E 32 4 Outdoor unit installation and construction ...
Страница 120: ...Construction E 33 4 Outdoor unit installation and construction ...
Страница 121: ...Construction E 34 4 Outdoor unit installation and construction ...
Страница 122: ...Construction E 35 4 Outdoor unit installation and construction ...
Страница 123: ...Construction E 36 4 Outdoor unit installation and construction ...
Страница 124: ...Construction E 37 4 Outdoor unit installation and construction ...
Страница 127: ...Construction E 40 5 Commissioning ...
Страница 128: ...Construction E 41 5 Commissioning ...
Страница 129: ...Construction E 42 5 Commissioning ...
Страница 130: ...Construction E 43 5 Commissioning ...
Страница 131: ...Construction E 44 5 Commissioning ...
Страница 132: ...Construction E 45 5 Commissioning ...
Страница 133: ...Construction E 46 5 Commissioning ...
Страница 134: ...Construction E 47 5 Commissioning ...
Страница 135: ...Construction E 48 5 Commissioning ...
Страница 136: ...Construction E 49 5 Commissioning ...
Страница 137: ...Construction E 50 5 Commissioning ...
Страница 138: ...Construction E 51 5 Commissioning ...
Страница 139: ...Construction E 52 5 Commissioning ...
Страница 140: ...Construction E 53 5 Commissioning ...
Страница 141: ...Construction E 54 5 Commissioning ...
Страница 142: ...Construction E 55 5 Commissioning ...
Страница 143: ...Separately Contents 1 Parts for the outdoor unit 1 Exhaust extension kit F 2 F 1 ...
Страница 150: ...Periodicinspection G 3 1 Periodic maintenance contract 70 90 Type 120 150 190 Type ...
Страница 154: ...Water heat exchange unit H 4 2 System characteristics Water heat exchanger unit connection limitations ...
Страница 155: ...Water heat exchange unit H 5 3 External view ...
Страница 158: ...Water heat exchange unit H 8 4 Specification 2 External dimension diagram ...
Страница 160: ...Water heat exchange unit H 10 4 Specification 4 Power characteristics 1Performance characteristics graph ...
Страница 161: ...Water heat exchange unit H 11 4 Specification ...