Details of Self-Diagnostics
When the operation selector on the indoor unit is moved from the ON or TEST position to the OFF (Self-diagnostics)
position, the indicator lamps on the indoor unit will flash (or remain ON) for 5 seconds and then turn OFF for 2 seconds
(buzzer sounds once) to indicate the presence of a sensor failure or the activation of a protective function.
Self-diagnostics is completed when the buzzer sounds 3 beeps.
If there is no trouble, the lamps do not flash (illuminate). Also note that the corresponding parts listed below may not be
present in some models.
Indication on indoor unit
Timer
Operation
Room temperature sensor failure
Code
Diagnostics item
Diagnostics contents
Indoor heat exchanger sensor failure
Humidity sensor failure
Compressor temperature sensor failure
SH sensor failure
Outdoor heat exchanger sensor failure
Outdoor narrow tubing sensor failure
Outdoor air temperature sensor failure
Outdoor wide tubing sensor failure
Outdoor electrical current sensor failure
Indoor/outdoor communications failure
(serial communications)
HIC circuit failure
Power Tr circuit failure
Outdoor unit external ROM failure
Peak current cut-off
PAM circuit failure
Active circuit failure
Compressor discharge overheat
prevention
Indoor fan operating failure
4-way valve switching failure
Indoor zero-cross failure
DC compressor drive circuit failure
No-refrigerant protection
Outdoor AC fan operating failure
Outdoor system communications failure
Outdoor high-voltage SW, OLR operation
Outdoor power supply open phase,
outdoor col freezing
Freeze-prevention operation
Outdoor circuit board failure
*
Miswiring
*
AC power failure
*
Blown fuse
*
Power relay failure
*
Indoor or outdoor circuit board failure
*
HIC or power Tr failure
*
Outdoor fan does not turn
*
Instantaneous power outage
*
Service valve not opened
*
Outdoor fan blocked
*
Continuous overload operation
*
Compressor failure
*
Outdoor circuit board failure
*
Instantaneous power outage
*
HIC or power Tr failure
*
Outdoor circuit board failure
*
Outdoor circuit board failure
*
Outdoor power supply voltage failure
*
Electric expansion valve failure
*
Capillaries blocked
*
No gas
*
Continuous
overload operation
*
Outdoor fan does not turn
*
Outdoor circuit board failure
*
Fan motor failure
*
Contact failure at connector
*
Indoor circuit board failure
*
Miswiring
*
Blown fuse
*
Power relay failure
*
Open phase
*
Outdoor circuit board failure
*
Compressor failure
*
Indoor fan system failure
*
No refrigerant
*
Low-temperature operation
Other: Timer lamp flashes (3-second intervals).
NOTE: If the operation lamp continues to flash (orange) even when the indoor unit operation selector has been moved
to the OFF position, an indoor unit external ROM failure has occurred. (E14)
After inspection or repair is completed, be sure to move the operation selector to the DEMO position, turn the
power ON, and erase the diagnostics contents.
S01
S02
S03
S04
S05
S06
S07
E01
E02
E03
E04
E05
E06
E07
E08
E09
E10
E11
E12
E13
Sensor open circuit or short circuit
Contact failure at connector or open circuit at teminal
crimping location (short-circuit detection only for the
humidity sensor)
Indoor/outdoor circuit board failure
*
*
*
Sensor open circuit or short circuit
Contact failure at connector or opern circuit at terminal
crimping location
Outdoor circuit board failure
*
*
*
*
External ROM data failure
*
Outdoor circuit board failure
*
4-way valve failure
*
Outdoor circuit board failure
*
Service valve not opened
*
No refrigerant
*
Open phase
*
Outdoor circuit board failure
*
Fan motor failure
*
Contact failure at connector
*
Outdoor circuit board failure
...ON
...Flashing
...OFF