4.7 GROUP 4 PARAMETER SET UP: INPUT HIGH LIMIT
4.7.1 Programming Ranges and Default/ Factory Preset Values of Parameters Under Group 4 –
INPUT HIGH LIMIT
Table 4.8 below gives details of programming ranges and default values of parameters under Parameter Group 4 -
INPUT HIGH LIMIT.
Refer to Fig 4.3 under Section 4.1.3.2 for Menu Map for navigating through various parameters
under this Group 4
.
Table 4.8 Group 4 Parameter Set Up: INPUT HIGH LIMIT
(Refer to Menu Map at Fig 4.3, Section 4.1.3.2)
Parameter
Setup Screen
No.
(Column 1)
Parameter
(Column 2)
Setting range
• EVO-1212F/1212F-HW/1224F
/1224F-HW
•EVO-2212 / 3012 / 2224 / 4024
(Column 3)
EVO-2212E / 3012E / 2224E /
4024E
(Column 4)
EVO-4248SP
(Column 5)
1
RESET VOLTAGE
120.0 - 150.0V
(Default:125.0V)
200.0 - 280.0V
(Default:260.0V)
120.0 - 350.0V
(Default:265.0V)
2
CUT OFF VOLT 1
120.0 - 150.0V
(Default: 135.0V)
200.0 - 280.0V
(Default:265.0V)
120.0 - 350.0V
(Default:270.0V)
3
DETECT TIME 1
0 - 2000 cycles
(Default: 60 cycles)
0 - 2000 cycles
(Default: 60 cycles)
0 - 2000 cycles
(Default: 60 cycles)
4
CUT OFF VOLT 2
120.0 - 150.0V
(Default: 140.0V)
200.0 - 280.0V
(Default:270.0V)
120.0 - 350.0V
(Default:275.0V)
5
DETECT TIME 2
0 - 2000 cycles
(Default: 15 cycles)
0 - 2000 cycles
(Default: 15 cycles)
0 - 2000 cycles
(Default: 15 cycles)
6
CUT OFF VOLT 3
120.0 - 150.0V
(Default: 145.0V)
200.0 - 280.0V
(Default:275.0V)
120.0 - 350.0V
(Default:280.0V)
7
DETECT TIME 3
0 - 2000 cycles
(Default: 1 cycle)
0 - 2000 cycles
(Default: 1 cycle)
0 - 2000 cycles
(Default: 1 cycle)
4.7.2 Description of Parameters Under Group 4 – INPUT HIGH LIMIT
4.7.2.1 RESET VOLTAGE
(Table 4.8, Parameter Setup Screen No.1)
This is the reset voltage at which the unit will revert to "Charging Mode" after it has switched over to "Inverting Mode"
due to input AC voltage rising to "CUT-OFF VOLT 1/CUT-OFF VOLT 2/CUT-OFF VOLT 3.
4.7.2.1.1 Programming Steps for Parameter "RESET VOLTAGE"
ð
ð
E V O - 1 2 1 2 F
I n v e r t i n g
A C
o u t p u t :
1 2 0 . 0 V
< 0 . 1 0 A
6 0 . 0 0 H z
Enter Key
Enter Key
Any Operating Mode Screen from
Fig 3.1 to 3.8
[Above screen is Screen 1 of Fig 3.2(a)]
Password 8052
See Section 4.3.1
See Table 4.8, Parameter Setup
Screen No. 1
for programmable range
S e l e c t
G r o u p
*
C H A R G E
C U R V E
ð
S e l e c t
P a r a m e t e r
*
I N P U T
H I G H
L I M I T
ð
S e l e c t
P a r a m e t e r
I N P U T
H I G H
L I M I T
*
R E S E T
V O L T A G E
1 2 5 . 0 V
Down Key x 3 times
Enter Key
S e l e c t
P a r a m e t e r
I N P U T
H I G H
L I M I T
*
R E S E T
V O L T A G E
1 2 5 . 0 V
P a s s w o r d
k e y
i n
0 0 0 0
ð
Enter Key