74 | SAMLEX AMERICA INC.
SECTION 4 |
Parameter Setup
4.4.2.22.3 Programming Steps for Parameter “BATTERY TYPE”
ð
ð
E V O - 1 2 1 2 F
I n v e r t i n g
A C
o u t p u t :
1 2 0 . 0 V
< 0 . 1 0 A
6 0 . 0 0 H z
Enter Key
Enter Key
Any Operating Mode Screen from
Fig 3.1 to 3.8
[Above screen is Screen 1 of Fig 3.2(a)]
Password 8052
See Section 4.3.1
See Table 4.3, Parameter Setup
Screen No. 22 for
programmable options
S e l e c t
G r o u p
*
C H A R G E
C U R V E
ð
S e l e c t
P a r a m e t e r
C H A R G E
C U R V E
*
B U L K C U R R E N T
2 0 A
ð
S e l e c t
P a r a m e t e r
C H A R G E
C U R V E
*
B A T T E R Y
T Y P E
0 = L e a d
A c i d
S e l e c t
P a r a m e t e r
C H A R G E
C U R V E
*
B A T T E R Y
T Y P E
0 = L e a d
A c i d
Enter Key
Down Key x 21 times
P a s s w o r d
k e y
i n
0 0 0 0
ð
Enter Key
4.4.2.23 SAFE CHARGING
(Table 4.1, Parameter Setup Screen No. 23)
4.4.2.23.1 General Information
Programming parameter “SAFE CHARGING” is a Timer
(0 to 300 min; Default: 0 min)
that may be used for the
following operational conditions / requirements:
a) The unit is programmed to operate in Normal
(Off-line)
Mode
(Parameter MODE set to “0= Normal” – See
Section 4.4.2.13)
i.e. AC input power is the primary source of AC power and EVO’s Inverter Section is the
backup source.
b) The AC load(s) that are fed with backup power from EVO
TM
have very high inrush current.
c) When AC input power is restored during “Battery low voltage!” fault condition
(Section 7, Srl. 1 of Table 7.1)
,
EVO
TM
will exit fault condition and change to “Charging Mode”
(say, “Condition 1”)
. The AC input power
may fail again within a short period of time and EVO
TM
will immediately revert back to “Inverting Mode”
(say,
“Condition 2”)
. During “Condition 1”, the battery voltage may not have risen appreciably higher than the
“BATT LOW VOLTAGE” threshold
(Section 4.4.2.9)
. Hence, during “Condition 2”, there would be
MORE
likelihood that high inrush current from the AC load(s) would drag the battery voltage down to (i) 9V or
lower for EVO-1212F/ 1212F-HW/ 2212/ 2212E/ 3012/ 3012E or, (ii)18V or lower for EVO-1224F/ 1224F-HW/
2224/ 2224E/ 4024/ 4024E or, (iii) 36V or lower for EVO-4248SP. This may trigger “Battery ultra low volt!”
fault condition
(Section 7, Srl. 2 of Table 7.1)
. It is, therefore, desirable that when AC input power is restored
during “Battery low voltage!” fault condition
(Condition 1)
and fails again
(Condition 2)
, the AC load(s) should
NOT be transferred to the Inverter Section
(under Condition 2)
till the AC input power had been restored
(under Condition 1)
for a minimum safe charging time period set through Timer “SAFE CHARGING”
(Section
4.4.2.23).
4.4.2.23.2 Initial Settings:
• As an example, assume that the timer associated with parameter “SAFE CHARGING”
(Section 4.4.2.23)
is set to
> the Default setting of 0 min, say “t” min
• Parameter “LV CUT OFF TIME”
(Section 4.4.2.11.2)
is set to 0 sec to ensure that the unit does not shut down
completely if AC input is not restored before expiry of time set through programming parameter “LV CUT OFF
TIME”
(Section 4.4.2.11)