background image

 

   

SAMLEX AMERICA INC.  |  105

SECTION 4  | 

 

Parameter Setup

4.8.2.9.1 Programming Steps for Parameter "DEFAULT RESET"

ð

ð

E V O - 1 2 1 2 F

I n v e r t i n g

A C

o u t p u t :

1 2 0 . 0 V

< 0 . 1 0 A

6 0 . 0 0 H z

Enter Key

Any Operating Mode Screen from 

Fig 3.1 to 3.8

[Above screen is Screen 1 of Fig 3.2(a)]

Password 8052 

See Section 4.3.1

For programming options, see Table 4.9:

• Screen No.8 (Column 1) for  

EVO-1212F/1212F-HW/1224F/1224F-HW

• Screen No.9 (Column 2) for  

EVO-2212/2212E/3012/3012E/2224/2224E/4024/

4024E & EVO-4248SP

S e l e c t

G r o u p

*

C H A R G E

C U R V E

ð

S e l e c t

P a r a m e t e r

*

O T H E R

F U N C T I O N

ð

S e l e c t

P a r a m e t e r

O T H E R

F U N C T I O N

*

P O

W

E R

S A V I N G

0 = D i s a b l e

S e l e c t

P a r a m e t e r

O T H E R

F U N C T I O N

*

B U Z Z E R

1 = O n

Down Key x 4 times

Enter Key

P a s s w o r d

k e y

i n

0 0 0 0

ð

Enter Key

S e l e c t

P a r a m e t e r

O T H E R

F U N C T I O N

*

B U Z Z E R

1 = O n

ð

Enter Key

4.8.2.10 DATALOG TIME AND DATALOG DISABLE 

(Table 4.9, (i) Parameter Setup Screen No. 9 under Column 1 (ii) Parameter Setup Screen No. 10 under Column 2)

Refer to Sections 5.2 to 5.3 on Data Logging. 
Data Logging uses external SD Card (

FAT 16/32, up to 32 GB capacity

) to record the values of various Operating 

Parameters /Events/Errors with Date and Time stamp controlled by an internal Real Time Clock (

RTC

). Parameters/

Events/Errors are recorded under “Data Logging Fields” (

Section 5.2.2 for information on Data Logging Fields for 

various EVO

TM

 Models

The recorded values of the various Operating Parameters are their “

Average Values

” computed from “Instantaneous 

Values” scanned over a programmable “time interval” set by programming parameter “DATALOG TIME”. Events/ 
Errors are recorded as soon as they are sensed. 

Apart from providing 6 options for setting the “time interval” for computing the “

Average Values

”, programming 

parameter “DATALOG TIME” is also used to disable Data Logging by selecting programming option “0=Disable”

Programming Options

 (i) 0=Disable, (ii) 1=1 sec (Default), (iii) 2=10 sec, (iv) 3=30 sec, (v) 4=60 sec, (vi) 5=5 min, (vii) 6=10 min

4.8.2.10.1 Programming Steps for Parameter "DATALOG TIME"

ð

ð

E V O - 1 2 1 2 F

I n v e r t i n g

A C

o u t p u t :

1 2 0 . 0 V

< 0 . 1 0 A

6 0 . 0 0 H z

Enter Key

Any Operating Mode Screen from 

Fig 3.1 to 3.8

[Above screen is Screen 1 of Fig 3.2(a)]

Password 8052 

See Section 4.3.1

For programming options, see Table 4.9:

• Screen No.9 (Column 1) for  

EVO-1212F/1212F-HW/1224F/1224F-HW

• Screen No.10 (Column 2) for  

EVO-2212/2212E/3012/3012E/2224/2224E/4

024/4024E & EVO-4248SP

S e l e c t

G r o u p

*

C H A R G E

C U R V E

ð

S e l e c t

P a r a m e t e r

*

O T H E R

F U N C T I O N

ð

S e l e c t

P a r a m e t e r

O T H E R

F U N C T I O N

*

P O

W

E R

S A V I N G

0 = D i s a b l e

S e l e c t

P a r a m e t e r

O T H E R

F U N C T I O N

*

D A T A L O G

T I M E

1 = 1 s e c

Down Key x 4 times

Enter Key

P a s s w o r d

k e y

i n

0 0 0 0

ð

Enter Key

S e l e c t

P a r a m e t e r

O T H E R

F U N C T I O N

*

D A T A L O G

T I M E

1 = 1 s e c

ð

Enter Key

(i) Down Key x 7 times for EVO-1212F/1212F-

HW/1224F/1224F-HW

(ii) Down Key x 8 times for EVO-2212/2212E/301

2/3012E/2224/2224E/4024/4024E  

& EVO-4248SP

(i) Down Key x 8 times for EVO-1212F/1212F-

HW/1224F/1224F-HW

(ii) Down Key x 9 times for EVO-2212/2212E/301

2/3012E/2224/2224E/4024/4024E  

& EVO-4248SP

Содержание EVO-RC-PLUS

Страница 1: ...olutionTM Series Inverter Charger Model EVO RC PLUS Please read this manual BEFORE operating Firmware Version 0 33 Owner s Manual NOTE REMOTE CONTROL MODEL NO EVO RC PLUS IS OPTIONAL AND IS REQUIRED TO BE ORDERED SEPARATELY ...

Страница 2: ...ORMATION PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION 2 ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSSES DAMAGES COSTS OR EXPENSES WHETHER SPECIAL DIRECT INDIRECT CONSEQUENTIAL OR INCIDENTAL WHICH MIGHT ARISE OUT OF THE USE OF SUCH INFORMATION THE USE OF ANY SUCH INFORMATION WILL BE ENTIRELY AT THE USERS RISK Samlex America reserves the right to revise this document and to periodically make cha...

Страница 3: ... 3 Blue LED Status 4 Red LED Fault 5 Navigation Key Back 6 Navigation Key Up 7 Navigation Key Down 8 Navigation Key Enter 9 SD Card Slot FAT16 32 format up to 32 GB 10 RJ 45 Jack 8P8C 11 RJ 12 Jack 6P6C Fig 1 1 Layout Dimensions of Remote Control Model EVO RC PLUS Pin Signal 1 12V 2 12V 3 ON OFF 4 D 5 D 6 NC 7 GND 8 GND Pin Signal 1 NC 2 GND 3 D 4 D 5 12 6 ON OFF 1 2 3 4 5 6 7 8 123456 View Lookin...

Страница 4: ...king Tab facing down Front view of Plug Locking Tab facing up Fig 1 2 Pin Out of Plugs for 8P8C RJ 45 Connecting Cable 8P 8C RJ 45 Modular Plug Pin Out of Plug End 2 Pin Out of Plug End 1 RJ 12 Pin Signal 6 ON OFF 5 12V 4 D 3 D 2 GND 1 NC RJ 45 Pin Signal 1 12V 2 12V 3 ON OFF 4 D 5 D 6 NC 7 GND 8 GND Fig 1 3 Pinout and internal interconnections of RJ 45 8P8C and RJ 12 6P6C Jacks on EVO RC PLUS Str...

Страница 5: ...1 2 3 4 5 6 1 2 3 4 5 6 7 8 Black Red Green Yellow Black Red Green Yellow NC Not connected NC 1 GND 2 D 3 D 4 12V 5 NC 6 1 NC 2 12V 3 NC 4 D 5 D 6 NC 7 GND 8 NC Rewired 8P8C Plug Locking tab facing down 6P4C Plug B 6P4C of Fig 1 4 has been cut and replaced with 8P8C plug and rewired as shown Connect to RJ 45 Jack marked Remote Control on i EVO 2212 3012 2224 4024 or ii EVO 2212E 3012E 2224E 4024E ...

Страница 6: ... 5 64 Fig 2 1 EVO RC PLUS Remote installation details 2 2 FLUSH MOUNT INSTALLATION To flush mount the wall opening must have at least 2 5 cm depth to make room for the remote and cable Also the thickness of wall panel board at the place of mounting should not be more than 13 mm to ensure that the RJ 45 RJ 12 Jack openings are not obstructed see Fig 2 3 EVO RC PLUS Installation Template 100 mm 3 94...

Страница 7: ...e Control Jack port on the EVO Inverter Charger 4 Take the other end of the remote cable and plug it into the RJ 45 RJ 12 Jack at the back of the EVO RC PLUS Fig 2 3 5 Check the remote display to ensure the Power up Self Test initiates 6 If the self test is successful secure the EVO RC PLUS to the wall using the four screws Fig 2 2 Flush mounting the EVO RC PLUS on the wall with 4 screws No 6 x 5 ...

Страница 8: ...See Section 4 9 for details ON OFF Key 2 The On Off Key is used for switching on switching off the EVO Inverter Charger and also to enter exit Standby Mode Navigation Keys 5 6 7 8 These four keys allow simple access to Menu Item that assists configuring monitoring and troubleshooting the EVO Inverter Charger o Navigation Key Functions Back Return to previous selection Up Scroll from lower to upper...

Страница 9: ...will power ON automatically and will start operating in Charging Mode If the AC input voltage and frequency are not within the programmed limits the units will power ON automatically and will start operating in Inverting Mode c To power OFF the EVO Inverter Chargers manually using the ON OFF Button on the front panel of the unit or the ON OFF Key on the Remote Control EVO RC PLUS there should be n...

Страница 10: ...creen b and the ID number which is found is shown at the end of the line When the default ID of 1 is found the display will then show the EVO Inverter Charger Model No and firmware version 3 digit number X XX Screen c The screen will then change to the Inverting Mode Screen Screen d or E V O 4 2 4 8 S P C h a r g i n g A C o u t 2 4 2 7 V 5 9 9 H z L 1 0 0 A L 2 0 0 A Screen d For EVO 4248SP or E ...

Страница 11: ...Standby Mode has been entered using EVO RC PLUS Remote Control it can ALSO be switched off using the On Off Push Button on the front panel of the EVOTM Inverter Charger Unit See Section 3 4 1 2 If EVO RC PLUS Remote Control has NOT been connected to the EVOTM Inverter Charger Unit Standby Mode cannot be entered using the On Off Push Button on the front panel of the EVOTM Inverter Charger Unit 3 4 ...

Страница 12: ...nt Panel of EVOTM Inverter Charger The Blue LED marked ON 12 Fig 2 1 of the EVOTM Inverter Charger Manual will blink once every 5 sec Red LED marked FAULT 13 Fig 2 1 of EVOTM Inverter Charger Manual and Buzzer will be off 3 4 1 2 Exiting Standby Mode Using EVO RC PLUS To exit Standby Mode using EVO RC PLUS press the On Off Key 2 Fig 1 1 momentarily 0 1 sec From Front Panel of EVOTM Inverter Charge...

Страница 13: ...e various screens all the screens covering a particular Operating Mode have been arranged in a Menu Map for example see Menu Map for Inverting Mode at Figs 3 2 a 3 2 b and 3 2 c Table 3 1 shows the names of the Operating Modes and the Fig Nos of the associated Menu Maps Typical Operating Mode Display Screen is shown in Fig 3 0 Example of Screen 1 of Inverting Mode Menu Map at Fig 3 2 a There are 4...

Страница 14: ... the AC input is avail able No inverting when the AC input is not available Fig 3 6 a Section 3 6 7 1 Fig 3 6 b Section 3 6 7 2 Fig 3 6 c Section 3 6 7 3 Charger Stop by BMS Applicable when BATTERY TYPE Option 1 Lithium is selected This mode is activated when the Lithium Battery Management System BMS sends command to EVO contact closure signal to stop charging to prevent battery over voltage or ov...

Страница 15: ... u t p u t 1 2 W 1 2 V A P F 0 0 0 0 Screen No 2 E V O 1 2 1 2 F S t a n d b y A C i n p u t 1 2 0 0 V 0 1 0 A 6 0 0 0 H z Screen No 3 E V O 1 2 1 2 F S t a n d b y B a t t e r y 1 2 0 0 V 0 0 A E x t e r n a l 0 0 A Screen No 5 E V O 1 2 1 2 F S t a n d b y B a t t e r y 2 5 0 C H e a t s i n k 2 5 0 C T r a n s f o r m e r 2 5 0 C Screen No 6 E V O 1 2 1 2 F S t a n d b y E V O V e r x x x I D 1...

Страница 16: ...2 E V O 3 0 1 2 S t a n d b y G r i d 1 2 0 0 V 0 1 0 A 6 0 0 0 H z Screen No 3 E V O 3 0 1 2 S t a n d b y G E N 1 2 0 0 V 0 1 0 A P F 6 0 0 0 H z Screen No 5 E V O 3 0 1 2 S t a n d b y G E N 1 2 W 1 2 V A P F 0 0 0 0 Screen No 6 E V O 3 0 1 2 S t a n d b y B a t t e r y 1 2 0 V 0 0 A E x t e r n a l 0 0 A E V O 3 0 1 2 S t a n d b y B a t t e r y 2 5 0 C H e a t s i n k 2 5 0 C T r a n s f o r ...

Страница 17: ...0 V 0 0 H z 0 1 5 A 0 1 5 A Screen No 1 E V O 4 2 4 8 S P S t a n d b y A C o u t p u t 1 8 W 1 8 W 1 8 V A 1 8 V A Screen No 2 E V O 4 2 4 8 S P S t a n d b y A C i n p u t 2 4 0 0 V 6 0 0 H z 0 1 5 A 0 1 5 A Screen No 3 E V O 4 2 4 8 S P S t a n d b y B a t t e r y 4 8 0 0 V 0 0 A E x t e r n a l 0 0 A Screen No 5 E V O 4 2 4 8 S P S t a n d b y B a t t e r y 2 5 0 C H e a t s i n k 2 5 0 C T r ...

Страница 18: ...3 Use Up ñ and Down ò Keys to navigate to the desired screen Up Key Down Key E V O 1 2 1 2 F I n v e r t i n g A C o u t p u t 1 2 0 0 V 1 0 0 0 A 6 0 0 0 H z Screen No 1 E V O 1 2 1 2 F I n v e r t i n g A C o u t p u t 1 2 0 0 W 1 2 0 0 V A P F 1 0 0 0 Screen No 2 E V O 1 2 1 2 F I n v e r t i n g A C i n p u t 1 2 0 0 V 0 1 0 A 6 0 0 0 H z Screen No 3 E V O 1 2 1 2 F I n v e r t i n g B a t t e...

Страница 19: ... t i n g G r i d 1 2 0 0 V 0 1 0 A 6 0 0 0 H z Screen No 3 E V O 3 0 1 2 I n v e r t i n g G E N 1 2 0 0 V 0 1 0 A P F 6 0 0 0 H z Screen No 5 E V O 3 0 1 2 I n v e r t i n g 1 2 W 1 2 V A P F 0 0 0 0 Screen No 6 E V O 3 0 1 2 I n v e r t i n g B a t t e r y 1 2 0 0 V 1 1 0 0 A E x t e r n a l 0 0 A Screen No 7 ð ð ð ð ð ð ð ð ð ð E V O 3 0 1 2 I n v e r t i n g G r i d 1 2 W 1 2 V A P F 0 0 0 0 S...

Страница 20: ...C o u t 2 4 W 2 4 V A Screen No 2 E V O 4 2 4 8 S P I n v e r t i n g A C i n 0 0 V 0 0 H z L 1 0 0 A L 2 0 0 A Screen No 3 E V O 4 2 4 8 S P I n v e r t i n g A C o u t 2 3 9 7 V 6 0 0 H z L 1 1 0 0 A L 2 1 0 0 A Screen No 5 E V O 4 2 4 8 S P I n v e r t i n g A C o u t L 1 1 2 0 0 W 1 2 0 0 V A L 2 1 2 0 0 W 1 2 0 0 V A Screen No 6 E V O 4 2 4 8 S P I n v e r t i n g E V O V e r X X X I D 1 R C ...

Страница 21: ...ion 3 6 8 and Figs 3 7 a to 3 7 c for details 3 The 3rd and the 4th lines show various operating parameters and their values 4 Use Up ñ and Down ò Keys to navigate to the desired screen Up Key Down Key E V O 1 2 1 2 F C h a r g i n g 0 B u l k S t a g e B a t t 1 2 0 0 V 2 0 0 A E x t e r n a l 0 0 A Screen No 1 E V O 1 2 1 2 F C h a r g i n g 0 B u l k S t a g e A C i n 1 2 0 0 V 1 0 0 0 A 6 0 0 ...

Страница 22: ...n No 1 E V O 3 0 1 2 C h a r g i n g 0 B u l k S t a g e A C i n 1 2 0 0 V 1 0 0 0 A 6 0 0 0 H z Screen No 2 E V O 3 0 1 2 C h a r g i n g 0 B u l k S t a g e G r i d 1 2 0 0 V A 1 2 0 0 W P F 1 0 0 Screen No 3 E V O 3 0 1 2 C h a r g i n g 0 B u l k S t a g e A C o u t 1 2 0 0 V A 1 2 0 0 W P F 1 0 0 Screen No 5 E V O 3 0 1 2 C h a r g i n g 0 B u l k S t a g e G E N 1 2 0 0 V 1 0 0 0 A 6 0 0 0 H...

Страница 23: ... n a l 0 0 A Screen No 1 E V O 4 2 4 8 S P C h a r g i n g T o t a l P o w e r A C i n 1 2 0 0 W 1 2 0 0 V A A C o u t 1 5 0 W 1 5 0 V A Screen No 2 E V O 4 2 4 8 S P C h a r g i n g A C i n 2 4 0 0 V 6 0 0 H z L 1 5 0 A L 2 5 0 A Screen No 3 E V O 4 2 4 8 S P C h a r g i n g A C o u t 2 4 0 0 V 6 0 0 H z L 1 0 6 A L 2 0 6 A Screen No 5 E V O 4 2 4 8 S P C h a r g i n g A C o u t L 1 7 5 W 7 5 V A...

Страница 24: ...Yes 0 Absorption Stage Constant Voltage Absorption Stage Parameter CHARGING PROFILE option 0 3 Stage Adaptive 1 Absorption Stage Constant Voltage Absorption Stage Parameter CHARGING PROFILE option 1 3 Stage Type 1 2 Absorption Stage Constant Voltage Absorption Stage Parameter CHARGING PROFILE option 2 3 Stage Type 2 3 Absorption Stage Constant Voltage Absorption Stage Parameter CHARGING PROFILE op...

Страница 25: ...lues 3 Use Up ñ and Down ò Keys to navigate to the desired screen Up Key Down Key E V O 1 2 1 2 F P o w e r S a v e A C o u t p u t 0 0 V 0 1 0 A 6 0 0 0 H z Screen No 1 E V O 1 2 1 2 F P o w e r S a v e A C o u t p u t 1 2 W 1 2 V A P F 0 0 0 0 Screen No 2 E V O 1 2 1 2 F P o w e r S a v e A C I n p u t 1 2 0 0 V 0 1 0 A 6 0 0 0 H z Screen No 3 E V O 1 2 1 2 F P o w e r S a v e B a t t e r y 1 2 ...

Страница 26: ... a v e G r i d 1 2 0 0 V 0 1 0 A 6 0 0 0 H z Screen No 3 E V O 3 0 1 2 P o w e r S a v e G E N 1 2 0 0 V 0 1 0 A P F 6 0 0 0 H z Screen No 5 E V O 3 0 1 2 P o w e r S a v e G E N 1 2 W 1 2 V A P F 0 0 0 0 Screen No 6 E V O 3 0 1 2 P o w e r S a v e B a t t e r y 1 2 0 0 V 0 0 A E x t e r n a l 0 0 A Screen No 7 ð ð ð ð ð ð ð ð ð ð E V O 3 0 1 2 P o w e r S a v e G r i d 1 2 W 1 2 V A P F 0 0 0 0 S...

Страница 27: ... v e T o t a l P o w e r A C i n 0 W 0 V A A C o u t 0 W 0 V A Screen No 2 E V O 4 2 4 8 S P P o w e r S a v e A C i n 0 0 V 0 0 H z L 1 0 0 A L 2 0 0 A Screen No 3 E V O 4 2 4 8 S P P o w e r S a v e A C o u t 0 8 V 6 0 0 H z L 1 0 0 A L 2 0 0 A Screen No 5 E V O 4 2 4 8 S P P o w e r S a v e A C o u t L 1 0 W 0 V A L 2 0 W 0 V A Screen No 6 E V O 4 2 4 8 S P P o w e r S a v e E V O V e r x x x I...

Страница 28: ...These 2 screens will switch every 2 sec These 2 screens will switch every 2 sec E V O 1 2 1 2 F O n l i n e A C o u t p u t 0 0 V 0 1 0 A 0 0 0 0 H z E V O 4 2 4 8 S P O n l i n e A C o u t p u t 0 0 V 0 0 H z 0 1 5 A 0 1 5 A E V O 1 2 1 2 F O n l i n e A C o u t p u t 1 2 0 0 V 0 1 0 A 6 0 0 0 H z E V O 4 2 4 8 S P O n l i n e A C o u t p u t 2 4 0 0 V 6 0 0 H z 5 0 0 A 5 5 0 A Fig 3 5 a Example ...

Страница 29: ...AC input power is NOT available LCD message on the 2nd Line will be Inverter Off 2 The 2nd line shows message Inverter Off as explained at NOTE 1 2 above 3 The 3rd and the 4th lines show various operating parameters and their values 4 Use Up ñ and Down ò Keys to navigate to the desired screen Up Key Down Key E V O 1 2 1 2 F C h r g O n l y I n v e r t e r O f f B a t t 1 2 0 0 V 0 0 A E x t e r n ...

Страница 30: ... E V O 3 0 1 2 C h r g O n l y I n v e r t e r O f f B a t t 1 2 0 0 V 0 0 A E x t e r n a l 0 0 A Screen No 1 E V O 3 0 1 2 C h r g O n l y I n v e r t e r O f f G r i d 0 0 V 0 1 0 A 0 0 0 H z Screen No 2 E V O 3 0 1 2 C h r g O n l y I n v e r t e r O f f G r i d 1 2 V A 1 2 W P F 0 0 0 0 Screen No 3 E V O 3 0 1 2 C h r g O n l y I n v e r t e r O f f O u t 1 2 V A 1 2 W P F 0 0 0 0 Screen No 5...

Страница 31: ...es 4 Use Up ñ and Down ò Keys to navigate to the desired screen Up Key Down Key E V O 4 2 4 8 S P C h r g O n l y I n v e r t e r O f f B a t t 4 8 0 0 V 1 0 0 A E x t e r n a l 0 0 A Screen No 1 E V O 4 2 4 8 S P C h r g O n l y T o t a l P o w e r A C i n 5 0 0 W 5 0 0 V A A C o u t 0 W 0 V A Screen No 2 E V O 4 2 4 8 S P C h r g O n l y A C i n 1 2 0 0 V 6 0 0 H z L 1 0 0 A L 2 0 0 A Screen No ...

Страница 32: ... Off by BMS on the right This message is shown in two parts first Chgr Off and then by BMS Each part is switched every 2 sec 2 The 2nd line will show the following information For Screens Nos 1 to 5 Chgr Off by BMS For Screen Nos 6 Battery Temperature e g Battery 25 0C For Screen Nos 7 EVOTM Firmware Version and Communication ID e g EVO Ver X XX ID 1 3 The 3rd and the 4th lines show various operat...

Страница 33: ...x t e r n a l 0 0 A Screen No 1 E V O 3 0 1 2 C h g r S t o p C h a r g e r S t o p b y B M S A C i n 1 2 0 0 V 1 0 0 0 A 6 0 0 0 H z Screen No 2 E V O 3 0 1 2 C h g r S t o p C h a r g e r S t o p b y B M S G r i d 1 2 0 0 V A 1 2 0 0 W P F 1 0 0 Screen No 3 E V O 3 0 1 2 C h g r S t o p C h a r g e r S t o p b y B M S A C o u t 1 2 0 0 V A 1 2 0 0 W P F 1 0 0 Screen No 5 E V O 3 0 1 2 C h g r S ...

Страница 34: ...V A A C o u t 3 W 3 6 V A Screen No 2 E V O 4 2 4 8 S P T o t a l P o w e r A C i n 3 6 W 3 6 V A A C o u t 3 W 3 6 V A Screen No 3 E V O 4 2 4 8 S P A C o u t 2 4 2 7 V 5 9 9 H z L 1 0 1 A L 2 0 1 A Screen No 5 E V O 4 2 4 8 S P A C o u t L 1 3 6 W 3 6 V A L 2 3 W 3 6 V A Screen No 6 E V O 4 2 4 8 S P E V O V e r x x x I D 1 R C V e r x x x Y Y Y Y M M D D H H M M Screen No 8 ð ð ð ð ð ð ð ð ð ð ...

Страница 35: ...ge is shown in two parts first Inv stop and then by BMS Each part is switched every 2 sec 2 The 2nd 3rd and the 4th lines show various operating parameters and their values 4 Use Up ñ and Down ò Keys to navigate to the desired screen Up Key Down Key E V O 1 2 1 2 F I n v S t o p A C o u t p u t 0 0 0 V 0 1 0 A 0 0 0 H z Screen No 1 E V O 1 2 1 2 F I n v S t o p A C o u t p u t 1 2 W 1 2 V A P F 0 ...

Страница 36: ... t o p G E N 1 2 W 1 2 V A P F 0 0 0 0 Screen No 6 E V O 3 0 1 2 I n v S t o p B a t t e r y 1 2 0 0 V 0 0 A E x t e r n a l 0 0 A E V O 3 0 1 2 I n v S t o p B a t t e r y 2 5 0 C H e a t s i n k 2 5 0 C T r a n s f o r m e r 2 5 0 C E V O 3 0 1 2 I n v S t o p E V O V e r x x x I D 1 R C V e r x x x Y Y Y Y M M D D H H M M Screen No 7 ð ð ð ð ð ð ð ð ð ð ð ð ð ð E V O 3 0 1 2 I n v S t o p G r i...

Страница 37: ...n 0 W 0 V A A C o u t 0 W 0 V A Screen No 3 E V O 4 2 4 8 S P I N V S t o p A C o u t 2 4 2 7 V 5 9 9 H z L 1 0 0 A L 2 0 0 A Screen No 5 E V O 4 2 4 8 S P I N V S t o p A C o u t L 1 0 W 0 V A L 2 0 W 0 V A Screen No 6 E V O 4 2 4 8 S P I N V S t o p B a t t e r y 2 5 0 C H e a t s i n k 2 2 8 C T r a n s f o r m e r 2 3 0 C Screen No 7 ð ð ð ð ð ð ð ð E V O 4 2 4 8 S P I N V S t o p A C i n 2 4 ...

Страница 38: ...r Remote Switch Multi function Relay etc 6 RC PLUS SETTINGS RC Plus Settings 7 TIME SETTING 1 parameter for Real Time Clock setting 8 STOP SD CARD NOTE Shown only when SD Card is inserted 1 parameter to stop SD Card access and to remove the SD Card The 1st screen for Select Group CHARGE CURVE will be accessed when Enter Key is pressed momentarily from any of the Operating Mode Display Screens deta...

Страница 39: ... H I G H L I M I T ð ð Screen No 2 for Group 2 Screen No 3 for Group 3 Screen No 4 for Group 4 Screen No 5 for Group 5 Screen No 6 for Group 6 Screen No 7 for Group 7 S e l e c t G r o u p S T O P S D C A R D ð ð Screen No 8 for Group 8 See NOTE 2 NOTES 1 Asterisk sign in the beginning of the 2nd line of the display screen points that the parameter shown in this line will be selected for further p...

Страница 40: ... 4 9 Group 7 TIME SETTING Fig 4 6 Section 4 1 3 5 Section 4 10 Group 8 STOP SD CARD Fig 4 6 Section 4 1 3 5 Section 4 11 NOTE Figs 4 2 to 4 4 show the default factory preset parameters for EVO 1212F 1212F HW For parameters for other Models refer to Tables shown under Column 3 of Table 4 2 For explanation of the format of the Select Parameter screen refer to Fig 4 2 Screen No 1 Select Parameter BUL...

Страница 41: ...T A G E S 0 N o Screen No 12 ð ð S e l e c t P a r a m e t e r C H A R G E C U R V E R E S E T T O B U L K 1 2 0 0 V Screen No 15 S e l e c t P a r a m e t e r C H A R G E C U R V E G S D E T E C T T I M E 1 0 s e c Screen No 16 ð ð ð ð S e l e c t P a r a m e t e r C H A R G E C U R V E G E N O N T I M E 6 0 m i n Screen No 17 S e l e c t P a r a m e t e r C H A R G E C U R V E G E N O F F D E L ...

Страница 42: ...t e r I N P U T H I G H L I M I T D E T E C T T I M E 3 1 c y c l e ð ð Parameter Group 2 INPUT SETTING Parameter Group 3 INPUT LOW LIMIT Parameter Group 4 INPUT HIGH LIMIT SECTION 4 Parameter Setup Fig 4 3 Select Parameter Menu Maps for i Parameter Group 2 INPUT SETTING ii Parameter Group 3 INPUT LOW LIMIT and iii Parameter Group 4 INPUT HIGH LIMIT NOTES 1 Value shown in the 4th line of the displ...

Страница 43: ...e c t P a r a m e t e r O T H E R F U N C T I O N B U Z Z E R 1 O n Screen No 7 S e l e c t P a r a m e t e r O T H E R F U N C T I O N D I S C H A R G E B E E P 1 O f f Screen No 8 ð ð ð ð S e l e c t P a r a m e t e r O T H E R F U N C T I O N T E M P U N I T 0 C S e l e c t P a r a m e t e r O T H E R F U N C T I O N P A S S W O R D D I S A B L E 0 D i s a b l e Screen No 12 Screen No 13 ð ð ð ...

Страница 44: ...arameter Group 8 STOP SD CARD 4 2 PARAMETER SETUP PROCEDURE 4 2 1 General Information Parameter Setup Procedure Please refer to Fig 4 7 The Enter key is used to enter Select Group Menu Map from any Operating Mode Screen shown in Figs 3 1 to 3 8 See Table 3 1 under Section 3 6 1 Example in Fig 4 7 starts with Inverting Mode Screen Screen 1 in Figs 3 2 a 3 2 b and 3 3 b After the Enter key is presse...

Страница 45: ...Menu Map Fig 4 1 Select Parameter Screen Figs 4 2 to 4 5 eg BULK CURRENT Screen No 1 Fig 4 2 Press Down Key Press Up Key Press Enter Key Press Back Key ð ð ð ð Screen No 2 for Group 2 Screen No 3 for Group 3 Screen No 4 for Group 4 Screen No 5 for Group 5 Screen No 6 for Group 6 Screen No 7 for Group 7 Screen No 8 for Group 8 ð ð ð ð NOTE Will be displayed only when SD Card is inserted Fig 4 7 Exa...

Страница 46: ...initiated the screen will display message Writing followed by message Write Success Please read Section 4 3 1 for example of programming a typical parameter BULK CURRENT i INFO 1 When the numerical value for any individual digit is changed that makes the overall numerical value of the parameter outside the programmable range an Exclamation Sign will appear on the left of the display screen warning...

Страница 47: ...abled see Section 4 3 2 P a s w o r d k e y i n 0 0 0 0 Password consisting of 4 digits 0000 will be requested as shown on the left NOTE Password to be entered is 8052 The first digit will have a blinking cursor _ Use Up Down Keys to scroll to number 8 for the first digit 8 of the password Momentarily press Enter Key Short press Digit 8 will be entered as the first digit of the Password and the bl...

Страница 48: ... the Enter Key HOLD for 3 to 4 sec and then release to write the new value of 50A into the memory W r i t e s u c c e s s Flashes twice when writing is successful S e t u p P a r a m e t e r C H A R G E C U R V E B U L K C U R R E N T 2 0 A End of setting Press Back Key to go back to the previous level Select Group CHARGE CURVE or Up Down Key to the other parameter s within the Select Parameter CH...

Страница 49: ...creen Select Parameter OTHER FUNCTION PASSWORD DISABLE 0 Disable Fig 4 4 will appear as on the left NOTE Default value is 0 Disable i e Disable the command DISABLE PASSWORD which means enable password protection 5 Press ENTER Key momentarily P a s w o r d k e y i n 0 0 0 0 Password consisting of 4 digits 0000 will be requested as shown on the left NOTE Password to be entered is 8052 The first digi...

Страница 50: ... Enter Key for longer time 3 to 4 sec to write the new selection 1 Enable W r i t e s u c c e s s New selection will be written with the message Write success as shown on the left S e l e c t G r o u p O T H E R F U N C T I O N P A S W O R D D I S A B L E 1 E n a b l e Screen as on left will appear confirming that the password has been disabled 8 Press Back Key two times to go back to the Operatin...

Страница 51: ...0 13 00V Default 10 50V 18 00 24 00V Default 21 00V 36 00 52 00V Default 42 00V 10 LV DETECT TIME Detect time to qualify low battery voltage as BATT LOW VOLTAGE condition 0 600 sec Default 10 sec 11 LV CUT OFF TIME Time in BATT LOW VOLTAGE condition to trigger complete shut down 0 7200 sec Default 1200 sec 12 EQUALIZE 4STAGES 4 Stage Charging On Off 0 No 1 Yes Default 0 No 13 MODE 0 Normal Default...

Страница 52: ... with the battery manufacturer regarding recommended Bulk Charging Current for your battery bank CAUTION WHEN SETTING BULK CURRENT FOR MODEL EVO 4248SP When the AC input voltage is 120 VAC Single Phase the Bulk Current setting of Model EVO 4248SP should be reduced to 30A This will prevent the unit from overheating due to unbalance when charging the battery bank and running pass through loads from ...

Страница 53: ...ii EVO 2224 EVO 2224E Reduce by 1A every 10 sec iv EVO 4024 EVO 4024E Reduce by 5A every 10 sec b Models EVO 1212F EVO 1212F HW EVO 1224F EVO 1224F HW and EVO 4248SP Power Transformer Temperature 130 C Reduce by 0 2 every 20 sec Heat Sink Temperature is 90 C Reduce by 0 2 every 20 sec 2 In case external Solar Charge Controller is also charging the batteries through DC input terminals marked EXT Ch...

Страница 54: ...programmable range S e l e c t G r o u p C H A R G E C U R V E ð S e l e c t P a r a m e t e r C H A R G E C U R V E B U L K C U R R E N T 2 0 A ð S e l e c t P a r a m e t e r C H A R G E C U R V E A B S O R P V O L T A G E 1 4 4 0 V S e l e c t P a r a m e t e r C H A R G E C U R V E A B S O R P V O L T A G E 1 4 4 0 V Enter Key Down Key x 1 time 4 4 2 3 EQUALIZE VOLTAGE Table 4 3 Screen No 3 Th...

Страница 55: ...Equalize Voltage Floating Voltage Batt Over Volt Restart Voltage Low Volt Alarm Batt Low Voltage when the Temperature Sensor is installed on the battery see Section 2 5 in the Owner s Manual for Evolution Series Inverter Charger CAUTIONS 1 Lithium Ion charging does not require temperature compensation Hence do not use EVO BCTS Temperature Sensor when charging Lithium Ion Batteries 2 Automatic temp...

Страница 56: ... the battery voltage drops to 0 5V below the set upper threshold of BATT OVER VOLT AC input is available and EVO Inverter Charger is operating in Charging Mode When the battery voltage rises to the set upper threshold of BATT OVER VOLT the Transfer Relay will be de energized charging and pass through will be stopped and PWM drive to the Inverter Section will be switched OFF Fault message Battery o...

Страница 57: ...ter Charger will beep once per second If automatic starting stopping of Generator is used with RELAY FUNCTION programmed at 2 Generator 0 Section 4 8 2 5 2 1 or 3 Generator 1 Section 4 8 2 5 2 2 or 4 Generator 2 Section 4 8 2 5 2 3 the Relay will turn ON if the battery voltage dips to the value of LOW VOLTAGE ALARM and remains at this level or lower for time period equal to the value of GS DETECT ...

Страница 58: ...w voltage fault condition will be cleared While in Battery low voltage fault condition Section 7 Table 7 1 Srl No 1 if AC input is made available before the expiry of LV CUT OFF TIME Section 4 4 2 11 the Battery low voltage fault condition will be cleared The EVO Inverter Charger will restart in Inverter Mode synchronize with the AC input and then transfer to the AC input at zero crossing It will ...

Страница 59: ... t e r C H A R G E C U R V E B U L K C U R R E N T 2 0 A ð S e l e c t P a r a m e t e r C H A R G E C U R V E B A T T L O W V O L T A G E 1 0 5 0 V S e l e c t P a r a m e t e r C H A R G E C U R V E B A T T L O W V O L T A G E 1 0 5 0 V Enter Key Down Key x 8 times P a s s w o r d k e y i n 0 0 0 0 ð Enter Key 4 4 2 10 LV DETECT TIME Table 4 3 Screen No 10 To prevent Battery low voltage fault an...

Страница 60: ...etup Screen No 11 for programmable range S e l e c t G r o u p C H A R G E C U R V E ð S e l e c t P a r a m e t e r C H A R G E C U R V E B U L K C U R R E N T 2 0 A ð S e l e c t P a r a m e t e r C H A R G E C U R V E L V C U T O F F T I M E 1 2 0 0 s e c S e l e c t P a r a m e t e r C H A R G E C U R V E L V C U T O F F T I M E 1 2 0 0 s e c Enter Key Down Key x 10 times P a s s w o r d k e y...

Страница 61: ...Chargers Series 3 The Adaptive Charging Algorithm measures the Bulk Stage Time T0 to automatically compute Absorption Stage Time T1 and Equalization Stage Time T2 This algorithm is fully effective only when there are no other external DC loads being supplied by the battery that may divert full or part of the BULK CURRENT resulting in undesired increase in Bulk Stage Time T0 and consequently undesi...

Страница 62: ...4 4 2 13 1 For more information on the applications of parameter MODE and its 3 options please refer to the following sections Section 4 6 5 of Owners Manual for Models EVO 1212F 1212F HW 1224F 1224F HW Section 4 8 5 of Owners Manual for Models i EVO 2212 3012 2224 4024 and ii EVO 2212E 3012E 2224E 4024E Section 4 6 5 of Owners Manual for Models EVO 4248SP 4 4 2 13 1 Charger Only Mode Table 4 3 Sc...

Страница 63: ...or some time and the screen will revert back to Chgr Only Mode Screen C h a r g e r O n l y I n v e r t e r O f f 4 4 2 13 2 Programming Steps for Parameter MODE ð ð E V O 1 2 1 2 F I n v e r t i n g A C o u t p u t 1 2 0 0 V 0 1 0 A 6 0 0 0 H z Enter Key Enter Key Any Operating Mode Screen from Fig 3 1 to 3 8 Above screen is Screen 1 of Fig 3 2 a Password 8052 See Section 4 3 1 See Table 4 3 Para...

Страница 64: ... Charge Controller Charging will be carried out till the batteries are charged as follows and then the Transfer Relay will be de energized to exit Charging Mode and revert back to Inverting Mode o For Parameter CHARGING PROFILE Section 4 4 2 21 set for 3 Stage Charging Profile as per i Option 0 3 Stg Adaptive ii Option 1 3 Stage Type 1 and iii Option 2 3 Stage Type 2 The Transfer Relay will be de ...

Страница 65: ... Parameter RESET TO BULK sets the value of battery voltage at which the charger will terminate the current charging stage of the selected CHARGING PROFILE restart charging from the beginning i e from the first BULK STAGE 4 4 2 15 1 Programming Steps for Parameter RESET TO BULK ð ð E V O 1 2 1 2 F I n v e r t i n g A C o u t p u t 1 2 0 0 V 0 1 0 A 6 0 0 0 H z Enter Key Enter Key Any Operating Mode...

Страница 66: ... 2 16 4 4 2 17 1 Programming Steps for Parameter GEN ON TIME ð ð E V O 1 2 1 2 F I n v e r t i n g A C o u t p u t 1 2 0 0 V 0 1 0 A 6 0 0 0 H z Enter Key Enter Key Any Operating Mode Screen from Fig 3 1 to 3 8 Above screen is Screen 1 of Fig 3 2 a Password 8052 See Section 4 3 1 See Table 4 3 Parameter Setup Screen No 17 for programmable range S e l e c t G r o u p C H A R G E C U R V E ð S e l e...

Страница 67: ...rogrammed duration of ABSORP TIME is excessively long Care should be taken to determine the time the battery is required to remain in Absorption Stage ABSORP TIME based on the application and then set programming parameter ABSORP TIME accordingly Programmable range is 0 600 min Default value is 60 min 4 4 2 19 1 Programming Steps for Parameter ABSORP TIME ð ð E V O 1 2 1 2 F I n v e r t i n g A C ...

Страница 68: ... follows 0 3 Stage Adaptive Default 1 3 Stage Type 1 2 3 Stage Type 2 3 2 Stage Type 1 4 2 Stage Type 2 5 2 Stage Type 3 NOTE 3 Stage Adaptive Charging Profile option 0 3 Stage Adaptive Shown as 0 3 Stg Adaptive in the programming screen is the default charging profile applicable for Lead Acid Batteries Details of the 6 programmable charging profiles under programming parameter CHARGING PROFILE ar...

Страница 69: ... falls to the programmed value of parameter RESET TO BULK For details of programming range procedure refer to Section 4 4 2 15 iii If the charger remains in the Float Stage for 10 days Lead Acid Flooded and sealed AGM Gel Cell ENSURE that there are no other DC load s on the batteries Load s on the battery may drain full or part of the charging current and will upset the Adaptive Time Algorithm for...

Страница 70: ...ameter RESET TO BULK For details of programming range procedure refer to Section 4 4 2 15 iii If the charger remains in the Float Stage for 10 days Lead Acid Flooded and Sealed AGM Gel Cell Lithium For details see Section 5 11 of Owner s Manuals for EVOTM Series Inverter Charger 4 3 2Stage Type1 1 Stage 1 Bulk Stage For details see Section 5 7 1 1 of the Owner s Manual for EVOTM Inverter Charger C...

Страница 71: ... of programming range procedure refer to Section 4 4 2 2 2 Stage 2 Absorption Stage For details see Section 5 7 2 of the Owner s Manuals for EVOTM Series Inverter Charger Charge at constant voltage the programmed value for parameter ABSORP VOLTAGE For details of programming range procedure refer to Section 4 4 2 2 Remain in Absorption Stage till the current reduces to value the programmed value of...

Страница 72: ...ing or stop inverting For this the BMS will normally use miniature Normally Open 1 Form A Open Drain Opto Isolated DC Solid State Relay SSR The Solid State Relay output terminals in the BMS are normally marked Drain of Mosfet Switch and Source of Mosfet Switch Example of this type of relay is IXYS Part No CPC1002N 60V 700mA rating The following 2 types of signals are normally used by the BMS for o...

Страница 73: ...continue to be passed through Internally the EVOTM will be in Charging Mode but the charging current will be reduced to 0A During this condition the Charging Mode Screens will display message Charger Off by BMS as follows EVO 1212F EVO 1212F HW EVO 1224F EVO 1224F HW Fig 3 7 a Section 3 6 8 1 i EVO 2212 EVO 3012 EVO 2224 EVO 4024 and ii EVO 2212E EVO 3012E EVO 2224E EVO 4024E Fig 3 7 b Section 3 6...

Страница 74: ...tery low voltage fault condition Section 7 Srl 1 of Table 7 1 EVOTM will exit fault condition and change to Charging Mode say Condition 1 The AC input power may fail again within a short period of time and EVOTM will immediately revert back to Inverting Mode say Condition 2 During Condition 1 the battery voltage may not have risen appreciably higher than the BATT LOW VOLTAGE threshold Section 4 4 ...

Страница 75: ...mentioned at Srl 5 above SAFE CHARGING Timer value has counted down to 0 min EVOTM will operate in Inverting Mode As the batteries were re charged for sizable time period the programmed time t of the SAFE CHARGING timer the battery would have charged appreciably higher than the BATT LOW VOLTAGE threshold Section 4 4 2 9 Hence there is LESS likelihood that high inrush current from the AC loads woul...

Страница 76: ...harging current from internal AC charger PLUS charging current from the External Solar Charge Controller o Charging current from the Internal AC Charger Programmed value of Parameter BULK CURRENT Section 4 4 2 1 MINUS value of charging current from the External Solar Charge Controller i Programming Parameter EXT CHARGER set at Option 1 Not affect Section 4 4 2 24 Total Charging Current Charging cu...

Страница 77: ...DEFAULT FREQ See NOTE 1 0 60Hz Default 60Hz 0 60Hz 1 50Hz Default 0 60Hz See NOTE 1 0 60Hz Default 0 60Hz 0 60Hz 1 50Hz Default 0 60Hz 0 50Hz 1 60Hz Default 0 50Hz 2 2 GRID MAX CURRENT 5 20A Default 20A 5 40A Default 30A 5 70A Default 30A 5 20A Default 20A 5 40A Default 30A 5 70A Default 30A 5 30A Default 30A 5 20A Default 16A 5 25A Default 16A 5 20A Default 16A 5 35A Default 16A See NOTE 2 3 GEN ...

Страница 78: ...G D E F A U L T F R E Q 0 6 0 H z Enter Key Enter Key P a s s w o r d k e y i n 0 0 0 0 ð Enter Key NOTES 1 Parameter DEFAULT FREQ is fixed al 60Hz for EVO 1212F 1212F HW EVO 1224F 1224F HW Option 0 60Hz These units cannot be set at 50Hz Option 1 50Hz If option 1 is entered for these models for 50Hz the screen line will show 1 xxHz meaning that Option 1 is invalid 2 For EVO 2212 3012 2224 4024 424...

Страница 79: ...meter is available ONLY for EVO 2212 2212E EVO 3012 3012E EVO 2224 2224E EVO 4024 4024E This parameter setting is NOT available for EVO 1212F EVO 1212F HW EVO 1224F EVO 1224F HW EVO 4248SP In Charging Mode the net AC input current from the AC input terminals marked GEN is the sum of the AC side charging current and the pass through load current Based on the rated capacity of the AC source connecte...

Страница 80: ...ter Charger will transfer to Inverting Mode 4 5 2 4 1 Programming Steps for Parameter HIGH CUT OFF ð ð E V O 1 2 1 2 F I n v e r t i n g A C o u t p u t 1 2 0 0 V 0 1 0 A 6 0 0 0 H z Enter Key Any Operating Mode Screen from Fig 3 1 to 3 8 Above screen is Screen 1 of Fig 3 2 a Password 8052 See Section 4 3 1 S e l e c t G r o u p C H A R G E C U R V E ð S e l e c t P a r a m e t e r I N P U T S E T...

Страница 81: ...e Section 4 3 1 S e l e c t G r o u p C H A R G E C U R V E ð S e l e c t P a r a m e t e r I N P U T S E T T I N G ð S e l e c t P a r a m e t e r I N P U T S E T T I N G D E F A U L T F R E Q 0 6 0 H z S e l e c t P a r a m e t e r I N P U T S E T T I N G L O W C U T O F F 5 5 H z Down Key x 1 time Enter Key P a s s w o r d k e y i n 0 0 0 0 ð Enter Key S e l e c t P a r a m e t e r I N P U T S ...

Страница 82: ...SP These options are i Option 0 Fine see Section 4 5 2 8 a below and ii Option 1 Coarse see Section 4 5 2 8 b below When EVO is operating in Inverting Mode there is no AC input its output frequency will be equal to the frequency that has been selected by the programming parameter DEFAULT FREQ TABLE 4 6 and Section 4 5 2 1 When AC input is made available it is first monitored for 2 sec If it is wit...

Страница 83: ...RONIZATION Only for EVO 1212F 1212F HW 1224F 1224F HW 4248SP ð ð E V O 1 2 1 2 F I n v e r t i n g A C o u t p u t 1 2 0 0 V 0 1 0 A 6 0 0 0 H z Enter Key Down Key x 6 times Any Operating Mode Screen from Fig 3 1 to 3 8 Above screen is Screen 1 of Fig 3 2 a Password 8052 See Section 4 3 1 For programmable options see Table 4 6 Parameter Setup Screen No 7 under Column 1 for EVO 1212F 1212F HW 1224F...

Страница 84: ...i First the frequency of the Inverter Section is tracked in steps of 0 1Hz per cycle and made equal to the frequency of the Grid Inverter Generator input ii Then the phase of the Inverter voltage relative to the Grid voltage is tracked by 1º per cycle When the phase of the Inverter voltage is within 3 5º of the input voltage waveform the Transfer Relay is activated to transfer the AC load from the...

Страница 85: ...8 9 in Fig 2 3 in Owner s Manuals for i EVO 2212 3012 2224 4024 and ii EVO 2212E 3012E 2224E 4024E This facilitates faster and safer transfer of power between the Inverter Section and the AC input source NOTE For supplementary details on synchronized transfer of AC power please refer to Section 4 5 4 to 4 5 7 of Owner s Manuals for i EVO 2212 3012 2224 4024 and ii EVO 2212E 3012E 2224E 4024E Param...

Страница 86: ...Input Terminals marked GEN 7 8 9 in Fig 2 3 in Owner s Manuals for i EVO 2212 3012 2224 4024 and ii EVO 2212E 3012E 2224E 4024E Synchronization control logic used in this option is suitable for more stable frequency output of Grid Inverter Generator Under this option the frequency and phase of the Inverter Section are synchronized with the Grid as follows i First the frequency of the Inverter Sect...

Страница 87: ...rrent is 1A more than the programmed value of GRID MAX CURRENT GEN MAX CURRENT for more than 5 sec Fault Mode will be activated There will be no AC output because the Transfer Relay will be de energized charging will be stopped and PWM drive to the Inverter Section will be switched off Fault message Input over current will be displayed on the LCD screen Blue LED marked Status will be switched off ...

Страница 88: ...e to 9V 18V 36V or below for 1 ms and trigger Battery ultra low voltage fault Under this condition the user may change to Option 1 Direct b Option 1 Direct Under this option the unit will directly start in Charging Mode 4 5 2 12 1 Programming Steps for Parameter INPUT RECOVERY ð ð E V O 1 2 1 2 F I n v e r t i n g A C o u t p u t 1 2 0 0 V 0 1 0 A 6 0 0 0 H z Enter Key Any Operating Mode Screen fr...

Страница 89: ...cycle 4 6 2 Description of Parameters Under Group 3 INPUT LOW LIMIT 4 6 2 1 RESET VOLTAGE Table 4 7 Parameter Setup Screen No 1 This is the reset voltage at which the unit will revert to Charging Mode after it has switched over to Inverting Mode due to input voltage falling to CUT OFF VOLT 1 CUT OFF VOLT 2 CUT OFF VOLT3 4 6 2 1 1 Programming Steps for Parameter RESET VOLTAGE ð ð E V O 1 2 1 2 F I ...

Страница 90: ...V E ð S e l e c t P a r a m e t e r I N P U T L O W L I M I T ð S e l e c t P a r a m e t e r I N P U T L O W L I M I T R E S E T V O L T A G E 1 0 5 0 V S e l e c t P a r a m e t e r I N P U T L O W L I M I T D E T E C T T I M E 1 3 0 0 c y c l e Down Key x 2 times Enter Key P a s s w o r d k e y i n 0 0 0 0 ð Enter Key S e l e c t P a r a m e t e r I N P U T L O W L I M I T D E T E C T T I M E 1...

Страница 91: ... Fig 3 2 a Password 8052 See Section 4 3 1 See Table 4 7 Parameter Setup Screen No 6 for programmable range S e l e c t G r o u p C H A R G E C U R V E ð S e l e c t P a r a m e t e r I N P U T L O W L I M I T ð S e l e c t P a r a m e t e r I N P U T L O W L I M I T R E S E T V O L T A G E 1 0 5 0 V S e l e c t P a r a m e t e r I N P U T L O W L I M I T C U T O F F V O L T 3 9 0 0 V Down Key x 2...

Страница 92: ...ETECT TIME 2 0 2000 cycles Default 15 cycles 0 2000 cycles Default 15 cycles 0 2000 cycles Default 15 cycles 6 CUT OFF VOLT 3 120 0 150 0V Default 145 0V 200 0 280 0V Default 275 0V 120 0 350 0V Default 280 0V 7 DETECT TIME 3 0 2000 cycles Default 1 cycle 0 2000 cycles Default 1 cycle 0 2000 cycles Default 1 cycle 4 7 2 Description of Parameters Under Group 4 INPUT HIGH LIMIT 4 7 2 1 RESET VOLTAGE...

Страница 93: ... 3 8 Above screen is Screen 1 of Fig 3 2 a Password 8052 See Section 4 3 1 See Table 4 8 Parameter Setup Screen No 3 for programmable range S e l e c t G r o u p C H A R G E C U R V E ð S e l e c t P a r a m e t e r I N P U T H I G H L I M I T ð S e l e c t P a r a m e t e r I N P U T H I G H L I M I T R E S E T V O L T A G E 1 2 5 0 V S e l e c t P a r a m e t e r I N P U T H I G H L I M I T D E ...

Страница 94: ... Operating Mode Screen from Fig 3 1 to 3 8 Above screen is Screen 1 of Fig 3 2 a Password 8052 See Section 4 3 1 See Table 4 8 Parameter Setup Screen No 6 for programmable range S e l e c t G r o u p C H A R G E C U R V E ð S e l e c t P a r a m e t e r I N P U T H I G H L I M I T ð S e l e c t P a r a m e t e r I N P U T H I G H L I M I T R E S E T V O L T A G E 1 2 5 0 V S e l e c t P a r a m e ...

Страница 95: ...R SAVING 0 Disable 1 Enable Default 0 Disable 2 2 ENTER POINT 4 50W Default 6W 4 50W Default 6W 4 50W Default 8W 4 50W Default 6W 4 50W Default 6W 4 50W Default 8W 4 50W Default 8W 3 3 WAKE UP POINT 5 50W Default 7W 5 50W Default 7W 5 50W Default 10W 5 50W Default 7W 5 50W Default 7W 5 50W Default 10W 5 50W Default 10W 4 4 REMOTE SWITCH 0 Button Type 1 Switch Type Default 0 Button Type See NOTE 1 ...

Страница 96: ...er Key Any Operating Mode Screen from Fig 3 1 to 3 8 Above screen is Screen 1 of Fig 3 2 a Password 8052 See Section 4 3 1 See Table 4 9 Parameter Setup Screen No 1 for programmable options S e l e c t G r o u p C H A R G E C U R V E ð S e l e c t P a r a m e t e r O T H E R F U N C T I O N ð S e l e c t P a r a m e t e r O T H E R F U N C T I O N P O W E R S A V I N G 0 D i s a b l e Down Key x 4...

Страница 97: ...ions 4 8 3 and 4 8 4 in Owner s Manual for EVO 4248SP If the unit is in Power Save Mode and the value of the AC power of the load rises to WAKE UP POINT the unit will quit Power Save Mode and will start operating in full voltage Inverting Mode 4 8 2 3 1 Programming Steps for Parameter WAKE UP POINT ð ð E V O 1 2 1 2 F I n v e r t i n g A C o u t p u t 1 2 0 0 V 0 1 0 A 6 0 0 0 H z Enter Key Down K...

Страница 98: ...l of EVO Inverter Charger 11 Fig 2 1 in EVO Inverter Charger Owner s Manual The Default Setting is 0 Button 2 If the On Off control is changed to external Remote Switch it will not be possible to switch On Off the EVO Inverter Charger from the front panel On Off Push Button because it will work with Switch Type Logic at Fig 4 8 it will be ON only as long as the Push Button is kept pressed and will...

Страница 99: ...t closure opening for automatic starting and stopping of generator through appropriate optional Generator Auto Start Stop Control Module Options 2 3 and 4 See Sections 4 8 2 5 2 1 to 4 8 2 5 2 3 The 3 contacts of the Status Relay are connected to 3 terminals of Terminal Block marked Status Relay 14 Fig 2 1 in the Owner s Manual for the Inverter Charger on the front panel The contacts are marked NO...

Страница 100: ...ut terminals of EVO 4248SP 2 3 4 8A in Fig 2 3 in the Owner s Manual for EVO 4248SP For installation details please refer to i Section 3 17 Fig 3 14 and Section 3 18 Figs 3 15A B in the Owner s Manuals for i EVO 2212 3012 2224 4024 or ii EVO 2212E 3012E 2224E 4024E and iii Section 3 17 Fig 3 13 in the Owner s Manual for EVO 4248SP i INFO It is recommended that GSCM Mini Series of Generator Start S...

Страница 101: ...energized to stop the Generator as soon as the battery bank is charged to the voltage threshold set by parameter FLOATING VOLTAGE Section 4 4 2 4 o For Parameter CHARGING PROFILE Section 4 4 2 21 set for 2 Stage Charging Profile as per Option 3 2 Stage Type 1 The Status Relay will be de energized to stop the Generator when the battery bank is charged to voltage threshold set by parameter ABSORP VO...

Страница 102: ...hes OFF EVO will change over to Inverting Mode NOTE The State of Charge of the battery after the Status Relay has been switched OFF de energized and Generator is stopped will be indeterminate 4 8 2 5 2 3 Option 4 Generator 2 This Option will start the Generator at LOW VOLT ALARM Section 4 4 2 8 and stop the Generator after the desired programmed value of run time of the Generator GEN ON TIME Secti...

Страница 103: ...ter Setup Screen No 6 under Column 2 Parameter COMM ID Communication ID sets the ID number for the COMM Port and EVO RC PLUS Remote Control 4 8 2 6 1 Programming Steps for Parameter COMM ID ð ð E V O 1 2 1 2 F I n v e r t i n g A C o u t p u t 1 2 0 0 V 0 1 0 A 6 0 0 0 H z Enter Key Any Operating Mode Screen from Fig 3 1 to 3 8 Above screen is Screen 1 of Fig 3 2 a Password 8052 See Section 4 3 1 ...

Страница 104: ...EEP provides option to switch on switch off this alarm signalling The default option is 1 On NOTE If parameter BUZZER Section 4 8 2 7 is set for option 0 Off the operation of the buzzer will be switched off and there will be no discharge beeping even if parameter DISCHARGE BEEP has been set for option 1 On 4 8 2 8 1 Programming Steps for Parameter DISCHARGE BEEP ð ð E V O 1 2 1 2 F I n v e r t i n...

Страница 105: ...rs are their Average Values computed from Instantaneous Values scanned over a programmable time interval set by programming parameter DATALOG TIME Events Errors are recorded as soon as they are sensed Apart from providing 6 options for setting the time interval for computing the Average Values programming parameter DATALOG TIME is also used to disable Data Logging by selecting programming option 0...

Страница 106: ...Steps for Parameter TEMP UNIT ð ð E V O 1 2 1 2 F I n v e r t i n g A C o u t p u t 1 2 0 0 V 0 1 0 A 6 0 0 0 H z Enter Key Any Operating Mode Screen from Fig 3 1 to 3 8 Above screen is Screen 1 of Fig 3 2 a Password 8052 See Section 4 3 1 For programming options see Table 4 9 Screen No 11 Column 1 for EVO 1212F 1212F HW 1224F 1224F HW Screen No 12 Column 2 for EVO 2212 2212E 3012 3012E 2224 2224E...

Страница 107: ...rs Under Group 6 RC PLUS SETTING Table 4 10 below gives details of programming ranges and default values of parameters under Parameter Group 6 RC PLUS SETTING Refer to Fig 4 5 under Section 4 1 3 4 for Menu Map for navigating through various parameters under this Group 6 These parameters are used to control dimming of LCD back lighting of Remote Control EVO RC PLUS Table 4 10 Group 6 Parameter Set...

Страница 108: ...er determines the level of brightness dimming of the LCD backlight of Remote Control EVO RC PLUS when the LCD display is in IDLE LCD LIGHT mode This mode of the LCD display is activated if any key on the EVO RC PLUS Remote Control has not been depressed for a time period set by parameter IDLE LCD TIMER see details at Section 4 9 2 3 The default setting is option 1 25 NOTE If the LCD display is in ...

Страница 109: ...P a s s w o r d k e y i n 0 0 0 0 ð Enter Key S e l e c t P a r a m e t e r R C P L U S S E T T I N G I D L E L C D T I M E R 5 m i n ð Enter Key 4 10 GROUP 7 PARAMETER SETUP TIME SETTING Please refer to Parameter TIME SETTING under Screen No 7 for Group 7 at Fig 4 1 under Section 4 1 2 Set up details are given below The Date and Time Format is Year Month Day Hour Minute 24 hour clock NOTE Passwor...

Страница 110: ...message Please remove SD Card appears If the SD card is not removed within 30 sec it will reset After the card is removed it reverts to the original operating screen 4 11 1 Programming Steps for Parameter STOP SD CARD ð ð E V O 1 2 1 2 F I n v e r t i n g A C o u t p u t 1 2 0 0 V 0 1 0 A 6 0 0 0 H z Enter Key Down Key x 1 time Any Operating Mode Screen from Fig 3 1 to 3 8 Above screen is Screen 1...

Страница 111: ...TA LOGGING 5 2 1 General Information Data Logging uses external SD Card See Section 5 1 above to record the values of various Operating Parameters Events Errors with Date and Time stamp controlled by an internal Real Time Clock RTC It is therefore necessary that before starting data logging the current Date and Time should be set if not set already by using parameter TIME SETTING Section 4 10 Oper...

Страница 112: ...Grid volt Input current Input VA Inputt watt Output freq Output Volt Output current Output VA Output watt Battery volt Battery current External current Battery temperature C Transformer temperature C Hear sink temperature 1 C Hear sink temperature 2 C Fan speed Mode Error code Charge stage Event Fig 5 1 Data Logging Fields for EVO 1212F 1212F HW 1224F 1224F HW 5 2 2 2 DATA LOGGING Fields for i EVO...

Страница 113: ... 1 sec Default 2 10 sec 3 30 sec 4 60 sec 5 5 min 6 10 min NOTE Data Logging Fields Error Code and Event shown in Figs 5 1 to 5 3 above record Error Code Event as soon as they occur 5 2 3 Operating Screens when SD Card is Inserted for Data Logging Data logging will be carried out automatically as soon as the SD Card is inserted in the SD Card Slot of EVO RC PLUS Provided parameter DATALOG TIME Sec...

Страница 114: ... Log Files The File Name Format is month day hour minute txt MMDDhhmm txt Each file has 512 rows of records Each row has multiple data fields as described at Section 5 2 2 Each file size is 128kb TABLE 5 1 Example of Data Log Folder in SD Card s Root Directory 5 3 2 Table 5 2 shows an example of the contents of one of the txt files opened with a general purpose Text Reader e g Microsoft Notepad Th...

Страница 115: ...l Click File Menu Tab on the top left hand corner Click Open from the Drop Down Menu Browse to the Directory where the Data Log Files downloaded from the SD Card are located Click on File Types List Box at the bottom right corner the List Box shows All Excel Files as default and select Text Files from the Drop Down Menu All Text Files txt will be displayed The screen will look like Fig 5 4 Fig 5 4...

Страница 116: ...Import Wizard Step 1 of 3 will be shown Fig 5 5 Choose Delimited File Type Fig 5 5 Screen showing Step 1 of 3 of Text Import Wizard in Excel Text Import Wizard Step 2 will appear See Fig 5 6 Choose Semicolon and click Finish button Fig 5 6 Screen showing Step 2 of 3 of Text Import Wizard in Excel ...

Страница 117: ...SAVE ð ð E V O 1 2 1 2 F I n v e r t i n g A C o u t p u t 1 2 0 0 V 0 1 0 A 6 0 0 0 H z Enter Key Any Operating Mode Screen from Fig 3 1 to 3 8 Above screen is Screen 1 of Fig 3 2 a Password 8052 See Section 4 3 1 For programming options see Table 4 9 Screen No 10 Column 1 for EVO 1212F 1212F HW 1224F 1224F HW Screen No 11 Column 2 for EVO 2212 2212E 3012 3012E 2224 2224E 4024 4024E EVO 4248SP S ...

Страница 118: ...d parameters then on inserting the card the Remote Control will ask to upload the Config File Press Enter Button to confirm or Back Button to cancel U p l o a d c o n f Y e s E n t e r k e y N o B a c k k e y Asks to confirm or cancel uploading of saved parameters Choose Yes by pressing Enter Key U p l o a d c o n f 1 Configuration uploading ...

Страница 119: ... Blink once in 1 sec interval OFF OFF Equalization charging Blink once in 1 sec interval OFF OFF Inverting ON OFF Beep once in 3 sec interval Default OFF Low battery alarm ON Blink once in 1 sec interval Beep once in 1 sec interval Power saving Blink once in 3 sec interval OFF OFF Standby Blink once in 5 sec interval OFF OFF Fault OFF ON ON NOTE Buzzer is available only in EVO Inverter Charger The...

Страница 120: ...teady The unit will get locked in this condition and will be required to be switched off as follows o The unit will automatically switch off after expiry of time set by parameter LV CUT OFF TIME See Section 4 4 2 11 LCD Display LED Buzzer will be OFF or o In case the time set by parameter LV CUT OFF TIME See Section 4 4 2 11 has not expired switch off the unit manually See Section 3 2 2 While in B...

Страница 121: ... the batteries are charged by external charger connected directly to the batteries or through the External Charger Input 3 4 in Fig 2 1 in the EVOTM Owner s Manual and the battery voltage recovers to the set threshold of parameter RESET VOLTAGE Section 4 4 2 7 before the expiry of time set by parameter LV CUT OFF TIME Section 4 4 2 11 while in Battery ultra low voltage fault condition the Inverter...

Страница 122: ...input current being drawn from the AC input source Input current Charging Current Pass Through Current to the load is 1A more than the set threshold of GRID MAX CURRENT Section 4 5 2 2 GEN MAX CURRENT Section 4 5 2 3 for 5 seconds current is sampled every 33 3 µs There will be no AC output because the Transfer Relay will be de energized charging will be stopped and PWM drive to the Inverter Sectio...

Страница 123: ...nverter Mode Short circuit protection is activated as follows i EVO 1212F 1212F HW 1224F 1224F HW The output current has exceeded the value of the rated output current leading to the output voltage dropping to 15 Vrms for 6 cycles ii EVO 2212 3012 2224 4024 and EVO 2212E 3012E 2224E 4024E The output current has exceeded the rated output current leading to the output voltage dropping to 15 Vrms for...

Страница 124: ... The Blue LED marked Status will be switched OFF and the Red LED marked Fault will be steady ON The buzzer in EVO Inverter Charger will beep steady If in Inverting Mode Inverter Section will be switched OFF If in Charging Mode the Transfer Relay will be de energized and the Inverter Section will be switched OFF Check that the fans are working properly there is no blockage of air suction and discha...

Страница 125: ...lay LED Indicators Blue Status Red Fault Input Output Jacks RJ 45 Modular Jack 8P8C RJ 12 Modular Jack 6P6C Cable Set Provided RJ 45 Data Cable Straight Wired 10 Meters 33 ft Environment Operating Temperature Range 20 C to 60 C Dimensions W X H X D mm 160 x 114 2 x 35 5 W X H X D inches 6 3 x 4 5 x 1 4 Weight Weight without cable 0 3 kg 0 6 lb Weight with cable 0 4 kg 1 0 lb SECTION 8 Specificatio...

Страница 126: ...mber that has been altered removed or modified in any way There is no warranty for defects or damages to equipment or parts caused by Installation alternation inspection or removal Normal wear and tear Abuse or misuse of the equipment including exposure to excessive heat salt or fresh water spray or water immersion Corrosion fire lightening biological infestations or Acts of God Repairs attempted ...

Страница 127: ...SAMLEX AMERICA INC 127 NOTES ...

Страница 128: ...Numbers Ph 1 800 561 5885 Fax 1 888 814 5210 Local Numbers Ph 604 525 3836 Fax 604 525 5221 Website www samlexamerica com USA Shipping Warehouses Kent WA Plymouth MI Canadian Shipping Warehouse Richmond BC Email purchase orders to orders samlexamerica com ...

Отзывы: