SAMLEX AMERICA INC. | 89
SECTION 4 |
Parameter Setup
Table 4.7 Group 3 Parameter Set Up: INPUT LOW LIMIT
(Refer to Menu Map at Fig 4.3, Section 4.1.3.2)
Parameter
Setup Screen
No.
(Column 1)
Parameter
(Column 2)
Setting range
• EVO-1212F/1212F-HW/1224F
/1224F-HW
•EVO-2212 / 3012 / 2224 / 4024
(Column 3)
EVO-2212E / 3012E / 2224E /
4024E
(Column 4)
EVO-4248SP
(Column 5)
1
RESET VOLTAGE
60.0 - 120.0V
(Default:105.0V)
140.0 - 200.0V
(Default:190.0V)
60.0 - 200.0V
(Default:195.0V)
2
CUT OFF VOLT 1
60.0 - 120.0V
(Default: 100.0V)
140.0 - 200.0V
(Default:180.0V)
60.0 - 200.0V
(Default:185.0V)
3
DETECT TIME 1
0 - 2000 cycles
(Default: 300 cycles)
0 - 2000 cycles
(Default: 300 cycles)
0 - 2000 cycles
(Default: 300 cycles)
4
CUT OFF VOLT 2
60.0 - 120.0V
(Default: 95.0V)
140.0 - 200.0V
(Default:170.0V)
60.0 - 200.0V
(Default:175.0V)
5
DETECT TIME 2
0 - 2000 cycles
(Default: 60 cycles)
0 - 2000 cycles
(Default: 60 cycles)
0 - 2000 cycles
(Default: 60 cycles)
6
CUT OFF VOLT 3
60.0 - 120.0V
(Default: 90.0V)
140.0 - 200.0V
(Default:160.0V)
60.0 - 200.0V
(Default:165.0V)
7
DETECT TIME 3
0 - 2000 cycles
(Default: 1 cycle)
0 - 2000 cycles
(Default: 1 cycle)
0 - 2000 cycles
(Default: 1 cycle)
4.6.2 Description of Parameters Under Group 3 – INPUT LOW LIMIT
4.6.2.1 RESET VOLTAGE
(Table 4.7, Parameter Setup Screen No.1)
This is the reset voltage at which the unit will revert to "Charging Mode" after it has switched over to "Inverting Mode"
due to input voltage falling to "CUT-OFF VOLT 1
/
CUT-OFF VOLT 2 / CUT-OFF VOLT3".
4.6.2.1.1 Programming Steps for Parameter "RESET VOLTAGE"
ð
ð
E V O - 1 2 1 2 F
I n v e r t i n g
A C
o u t p u t :
1 2 0 . 0 V
< 0 . 1 0 A
6 0 . 0 0 H z
Enter Key
Enter Key
Any Operating Mode Screen from
Fig 3.1 to 3.8
[Above screen is Screen 1 of Fig 3.2(a)]
Password 8052
See Section 4.3.1
See Table 4.7, Parameter Setup
Screen No. 1
for programmable range
S e l e c t
G r o u p
*
C H A R G E
C U R V E
ð
S e l e c t
P a r a m e t e r
*
I N P U T
L O
W
L I M I T
ð
S e l e c t
P a r a m e t e r
I N P U T
L O
W
L I M I T
*
R E S E T
V O L T A G E
1 0 5 . 0 V
Down Key x 2 times
Enter Key
S e l e c t
P a r a m e t e r
I N P U T
L O
W
L I M I T
*
R E S E T
V O L T A G E
1 0 5 . 0 V
P a s s w o r d
k e y
i n
0 0 0 0
ð
Enter Key
4.6.2.2 CUT OFF VOLT 1
(Table 4.7, Parameter Setup Screen No.2)
If during "Charging Mode", the AC input voltage falls below "CUT-OFF VOLT 1" for period > "DETECT TIME 1", the
EVO™ Inverter/Charger will transfer to Inverting Mode from "Charging Mode".